Specifications

230 en | Event Messages SCSI to SATA RAID Subsystem | Administrator’s Manual
F.01U.027.802 | V1 | 2006.11 Bosch Security Systems
Warning
Notification
Message Controller BBU Thermal Shutdown/Enter Sleep-Mode!
What Happens?
The following conditions will cause the charger circuits to enter a low-
power and self-protection state:
1. The temperature sensor on the charger circuit reports elevated
temperature reading (>= 45 degree Celsius).
2. The BBU (battery cell pack) has been charged for over 7 hours.
The BBU charger will enter a timer fault state.
What to Do? 1. Check proper ventilation within the subsystem. You may also
check the readings from other sensors within the enclosure. Air-
flow might have been disrupted by the absence of one or several
major modules or the failure of a cooling fan. Once the thermal
condition is improved, charging will resume automatically.
2. If a new battery module has been charged for over seven (7) hours
and this event is issued, you may remove and re-install the battery
module. An empty battery module may take more than 7 hours to
be fully charge. There is a timer embedded with the charger, doing
so can reset the timer. Charging will resume automatically.
Message Memory Not Sufficient to Fully Support Current Config.
What Happens? The installed memory size does not support current configuration. Try
using a DIMM module of a larger size.
What to Do? Check proper installation of the module or contact your RAID system
supplier for a certified module.
Message Board1 Cold Temperature Back to Non-Critical LVs(_(C))
What Happens? Board1 (usually the RAID controller main board) ventilation condition
is restored to normal.
What to Do? Check proper working condition and press ESC to clear the message.
Message +12V Upper Voltage Back within Acceptable Limits (_._V)
What Happens? +12V voltage dropped back within preset thresholds.
What to Do? Check proper working condition and press ESC to clear the message.
Message +12V Lower Voltage Back within Acceptable Limits (_._V)
What Happens? +12V voltage dropped back within preset thresholds.
What to Do? Check proper working condition and press ESC to clear the message.
Message Memory is Now Sufficient to Fully Support Current Config.
What Happens? Memory of a sufficient capacity is installed and the subsystem should
work properly.
What to Do? Check proper working condition and press ESC to clear the message.