DLP-12 Connecting to the ATLAS 890 External Input
Introduction
This DLP explains how to connect other equipment to the external input on the ATLAS 890. The external
input connector can sense a relay closure or the presence of -48 VDC.
Prerequisite Procedures
Before making this connection, the unit should be mounted in its permanent location.
Tools and Materials Required
Wire strippers
Small, straight slot screwdriver
22 or 24 AWG 2-conductor twisted pair cross connect wire
Connecting the External Input
1. To sense the relay closure, connect VOUT (-48VDC limited to 1 mA) to the COM of the relay to be
monitored (see Figure 3 on page 348). Connect INPUT to the normally open (NO) contact of the
device to detect when the relay is energized or the normally closed (NC) to detect when the relay is
de-energized (see Table 2).
2. To sense the presence of -48 VDC, connect INPUT to the source to be sensed.
To prevent electrical shock, do not install equipment in a wet location or during a
lightning storm.
Electronic modules can be damaged by static electrical discharge. Before handling modules,
wear an antistatic discharge wrist strap to prevent damage to electronic components. Place
modules in antistatic packing material when transporting or storing. When working on
modules, always place them on an approved antistatic mat that is electrically grounded.