User`s guide
106 Troubleshooting
Temperature is 
over limit
Critical none Critical
Temp is 
>54.5º C
(130.1º F)
■ A fan is faulty. Check status and 
correct.
■ Airflow is obstructed; vents are 
blocked.
■ One or more slots are empty.
■ Power supply is faulty. Check status 
and correct.
■ Room temperature is too high. If 
ambient temperature cannot be 
reduced in a reasonable time, turn off 
product to prevent shortened life.
■ Temperature sensor is faulty. 
Compare temperature reported by peer 
LCC.
Major Warning none Non-critical
Temp is 
>36º C
(96.8º F)
Temperature sensors are on the LCC and are independent of 
power supplies. Investigate temperature warnings 
immediately, before power supplies sense critical temperature 
and turn off.
Temperature is 
under limit
Critical none Critical 
Temps 
<9.5º C
(49.1º F)
■ Room temperature is too low.
■ Temperature sensor is faulty. 
Compare temperature reported by peer 
LCC.
Major Warning none Non-critical 
Temps 
<15.5º C
(59.9º F)
Voltage is over 
limit
Critical none Critical Power supply is faulty. Check status and 
correct.
Major Warning none Non-critical
Voltage is 
under limit
Critical none Critical Either power supply is faulty. Check 
status and correct.
Major Warning none Non-critical
Table 13. Troubleshooting Table
Problem 
Description
HW Event 
Category
LED
State
STM 
Status
Probable Cause/Solution