Specifications
4–8 Compaq StorageWorks HSG80 Array Controller ACS Version 8.5 Maintenance and Service Guide
Invalid cache. Mirrored-cache mode
discrepancy. This may
occur after you’ve installed
a new controller. Its
existing cache module is
set for mirrored caching,
but the new controller is
set for unmirrored
caching. (It may also occur
if the new controller is set
for mirrored caching but
its existing cache module
is not.)
SHOW THIS CONTROLLER
indicates “invalid cache.”
Spontaneous FMU message
displays: “Cache modules
inconsistent with mirror
mode.”
Connect a terminal to the
maintenance port on the
controller reporting the error
and clear the error with the
following command—all on
one line: CLEAR_ERRORS
THIS_CONTROLLER
NODESTROY
INVALID_CACHE.
Cache module may
erroneously contain
unflushed write-back data.
This may occur after
you’ve installed a new
controller. Its existing
cache module may
indicate that it contains
unflushed write-back data,
but the new controller
expects to find no data in
the existing cache module.
(This error may also occur
if you install a new cache
module for a controller that
expects write-back data in
the cache.)
SHOW THIS CONTROLLER
indicates “invalid cache.”
No spontaneous FMU
message.
Connect a terminal to the
maintenance port on the
controller reporting the error,
and clear the error with the
following command—all on
one line: CLEAR_ERRORS
THIS_CONTROLLER
DESTROY INVALID_CACHE.
See
HSG80 Array Controller
ACS Version 8.5 CLI
Reference Guide
for more
information.
Table 4–1 Troubleshooting Table (Sheet 4 of 7)
Symptom Possible Cause Investigation Remedy