7.2.2 Accessing FRUs, Rackmount Systems
Access rackmount FRUs as follows (refer to Figure 7-3):
WARNING: The system can weigh 27.45 kg (61 lb). To prevent injury and
equipment damage, ensure that only one system is extended out of the cabinet at any
one time and that the cabinet is stabilized before pulling the system out on its slides.
The adjustable leveling feet should be down and the cabinet’s stabilizing bar fully
extended before any component is extended out of the cabinet on slides.
Do not extend more than one slide assembly at a time; cabinet instability may result.
1. Perform an orderly shutdown of the operating system.
2. Set the On/Off button on the operator control panel to off.
3. Unplug the AC power cord.
4. Pull off the front bezel using the two finger holds.
5. Remove the two front screws.
6. Slide the enclosure out on its rails.
7. Remove the retaining screw indicated by the yellow label on the upper left side
of the front of the system.
8. Slide back and remove the top cover.