QuickSpecs
HP BladeSystem
c7000 Server Blade
Enclosure
Dimensions
Height
17.4 in (442 mm)
Width
17.6 in (447.04 mm)
Depth
32 in (813 mm)
Shipping Dimensions
Height
29.88 in (759 mm)
Width
23.88 in (607 mm)
Depth
39.88 in (1013 mm)
Single Phase
Enclosure Weight
Unboxed
192 lb (87 kg)
Shipping
235 lb (106.6 kg)
Three -Phase
Enclosure NA/JPN
Weight
Unboxed
222 lb (100.7 kg)
Shipping
265 lb (120.2 kg)
Three-Phase
Enclosure International
Weight
Unboxed
222 lb (100.7 kg)
Shipping
265 lb (120.2 kg)
DC Input Enclosure
Weight
Unboxed
151 lb (68.5 kg)
Shipping
194 lb (88 kg)
Max Enclosure Weight
(approximate)
Unboxed
450 lb (204 kg)
Shipping
493 lb (223.6 kg)
Temperature Range
Operating
50° to 95° F (10° to 35° C)
Non-Operating
-22° to 140° F (-30° to 60° C)
Relative Humidity
Operating
10 to 90% relative humidity (Rh), 28°C
(82.4°F) maximum wet bulb temperature,
non-condensing.
Non-Operating
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F)maximum wet bulb temperature,
non-condensing.
NOTE:
Operating temperature has an altitude derating of 1.8° F (1° C) per 1,000 ft (304.8 m). No
direct sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-
operating limit is 30,000 ft (9,144 m) or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is
based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.
Power
Input Requirements - Single Phase Model
Rated input frequency
50 to 60 Hz
2400W PSU
Rated input voltage
200 to 240 VAC
Rated input current
per power supply
13.9 A at 200 VAC
13.3 A at 208 VAC
12.6 A at 220 VAC
Rated input power
per power supply
2780 VA
Input Requirements - Three Phase NA/JPN
Model
Rated input voltage
200 to 208 VAC Line to Line
3-Phase Delta
Rated input frequency
50 to 60 Hz
2250W PSU
Max input current per line cord
22.6A at 200 VAC
21.8A at 208 VAC
Max input power
per line cord
7836VA Max
2400W PSU
Max input current per line cord
24A at 200 VAC
23.1A at 208 VAC
Max input power
per line cord
8340 VA Max
Input Requirements - Three Phase International
Model
Rated input voltage
346 VAC to 415 VAC Line to Line
200 VAC to 240 VAC Line to Neutral
3-Phase WYE
Rated input frequency
50 to 60 Hz
2250W PSU
Max input current per line cord
11.9 A at 220 VAC
10.9 A at 240VAC
Max input power
per line cord
7836 VA Max
2400W PSU
Max input current per line cord
12.6 A at 220 VAC
11.5 A at 240VAC
Max input power
per line cord
8340 VA Max
Input Requirements DC Power
Rated Input Voltage
36 to -72 VDC
Max Input Current per line cord
75A
Max Input Power per line Cord
2700W
Power Cords
Single Phase
IEC-320 C19-C20 1.22m (6 ft)
3-Phase NA/JPN
2 x NEMA L15-30p 2.44m (10 ft)
3-Phase International
2 x IEC-309 200/346 V - 240/415 V, 5-Pin, 6h 16A 2.44m (10 ft)
-48V DC Power
Terminal lug: 45DG 4AWG 1/4 2H
Two-hole lug
45 degree bend
0.25in. (6.4mm) stud hole size
0.63in. (16mm) hole spacing
Output
Specifications
(per power supply)
HP 2400W High Efficiency Hot-Plug Power Supply
200 - 240 VAC 2400 W 92% Efficiency
HP 2250W -48V DC Hot-Plug Power Supply
2250W
Acoustic Noise
Listed are the declared A-Weighted sound power levels (LWAd) and declared average bystander position A-Weighted sound pressure levels
(LpAm) when the product is operating in a 23°C ambient environment. Noise emissions were measured in accordance with ISO 7779 (ECMA
74) and declared in accordance with ISO 9296 (ECMA 109).
Idle
LWAd
7.1 Bels
LpAm
54 dBA
Operating
LWAd
7.2 Bels
LpAm
54 dBA
Option Kits
Power Supply Option
Shipping Dimensions
Height
8.75 in (223 mm)
Width
8.63 in (219 mm)
Depth
35.13 in (892 mm)
Weight
8.5 lbs (3.85 kg)
Fan Option Shipping
Dimensions
Height
8.75 in (223 mm)
Width
9.75 in (248 mm)
Depth
15.88 in (403 mm)
Weight
4.0 lbs (1.8 kg)
BladeSystem Onboard
Administrator Option
Shipping Dimensions
Height
2.50 in (63.5 mm)
Width
9.88 in (251 mm)
Depth
13.50 in (343 mm)
Weight
4.0 lbs (1.8 kg)
QuickSpecs
HP BladeSystem c7000 Enclosure
Technical Specifications
DA - 12810 Worldwide QuickSpecs — Version 35 — 1.9.2012
Page 15