Specifications

The Troubleshooting Guide tells you how to solve problems you may encounter with your
Compaq UPS.
Symptom Possible Cause What To Do
UPS will not start Line cord is not connected Connect line cord
Circuit breaker on rear Push circuit breaker button
panel is open
Wall socket is dead Test wall socket
Battery fuse or circuit open Contact service center
LED 5 is RED Ground wire or connection Have a qualified electrician establish
(Site Wiring Fault) does not exist in wall outlet grounding connection
Line & neutral wires are Have a qualified electrician correct
reversed in wall outlet the wiring
Flashing Battery DC overvoltage condition Call Customer Service
Service LED (LED 10)
and alarm won’t clear
LED 10 is RED Potential battery failure Let UPS go through a full charge
(Battery Service) cycle by keeping it plugged in for
24 hrs; push Test/Alarm Reset button
New battery improperly Check connections or call
connected Customer Service
UPS switches Input voltage in your Change UPS nominal input to match
frequently area differs from the local nominal
between battery UPS nominal
and AC input
LED 10 (Battery UPS out of service for a long Keep UPS connected to line for at
Service) is red period least 24 hrs.and then conduct self test
during initial start up
LED 11 is Overload condition because Determine if load(s) is defective or if
SOLID RED load is drawing too much too many loads are connected to UPS;
power if so,disconnect a load
LED 1 is Line is high;UPS in battery Correct input voltage problem if
SOLID RED* operation possible or be prepared to lose battery
power to your load(s) in approx.3 to 5
minutes (depending on configuration)
after Impending Low Battery LED
turns on
LED 4 is Line is low (power failure); Correct AC input problem if possible
SOLID RED UPS in battery operation or be prepared to lose battery power
to your load(s) in approx.3 to 5
minutes (depending on configuration)
after Impending Low Battery LED
turns on
LED 4 is Line has returned but Push Test/Alarm Reset
FLASHING RED reset was not pushed
*If the UPS continuously displays a solid red LED 1 or 4 above the AC Input symbol,input voltage range can be extended.
29
Troubleshooting