UPS Technology
What UPS technology is available with the Compaq UPS?
The Compaq UPS utilizes a line-interactive plus topology which features sine wave output
and superior input/output voltage regulation.This technology is inherently reliable and
highly efficient.The Compaq UPS can correct input voltage variations as low as -35% of
nominal voltage without transferring to the battery.This will ensure the battery is preserved
and ready for the next power anomaly.
Does the UPS have a transformer?
Yes.Its function is to provide buck and boost regulation as well as provide isolation between
the battery and the output.
Can I change the line cord that is provided with the UPS?
We strongly recommend,due to worldwide safety standards,that you do not remove or
change the line cords provided with the UPS.
Can I change the plug provided with the UPS?
Yes,as long as the new plug is rated the same voltage and amperage as the provided plug.
What does the ground fault indicator (LED # 5,front panel) tell me?
This would indicate a possible wiring error in the outlet to the UPS,which should be checked
by an electrician.In high voltage applications (240 V),however,this alarm is always on, even
in a correctly wired installation.If this is the case,it should be disabled.
When should I disable the SLEEP feature (LED # 9,front panel) ?
In lightly loaded applications that you wish to keep running (less than 5% load) the sleep
feature should be disabled.
28