Specifications

27
#1*
120/230 VAC nominal (ON)
#2
110/220 VAC nominal (OFF)
#3
127/240 VAC nominal (OFF)
#4
Extended Voltage (OFF)
#6
Low Battery Alarm (ON)
#7
Shutdown Delay (ON)
#8
AC Input Failure Alarm (ON)
#9
Sleep Mode (ON) (defaulted OFF on T700)
#11-14 Reserved for Future Use
#5
Site Wiring Fault Alarm (ON)
When lit, LED #16 indicates that
the selected LED (1-15) is ON.
#10
100/208 VAC nominal (OFF)
#15
Reset Default Settings
Self Test/Alarm Silencer
*LED #1: Indicates 100 volt mode on T700j
LED #10: Not applicable for T700 models
†
†
ON
OFF
Understanding UPS Configuration
In the Configure Mode,the LEDs allow factory-set defaults to be changed.A user may
wish to alter these functions if the AC input consistently fluctuates higher or lower than
the factory-set nominal input voltage.Other changeable functions include LEDs for
extended voltage,shutdown delay,sleep mode,low battery,and AC input failure. In the
Configure Mode,each LED represents a changeable function,with the control buttons
responsible for enabling or disabling them (see illustration below).
Questions & Answers
Where can I find definitions of the setting and instructions on how to change
the UPS configurations?
In the Compaq UPS user manual.
How do I get into configure mode?
Press the ON and Self Test/Alarm Silencer button at the same time to switch to configure
mode.Once in configure mode,use the ON button to scroll through the LEDs (LED will flash).
Then,to turn on or off a particular LED, simply press the Self Test/Alarm Silencer button
(while in configure mode).The light over the ON button will be green if the LED is on
and no light will appear if the LED is off.
Can I configure voltage settings via the front panel?
Yes,the front panel is the only place you can configure voltages other than the default setting
already programmed on the UPS.Refer to the above question on how to change these defaults.