Specifications

24
Electrical Input
Voltage
120 and 230 VAC nominal; see Model
Selection Guide for user selectable voltages
On Line Voltage Range
-30%,+20% for nominal; user selectable
extended range of -35%,+20%
Nominal Input Frequency
50/60 Hz auto-selection
(60 Hz only for 120 and 127 VAC)
Frequency Tolerance
Nominal ±3 Hz
Electrical Output
Power Levels
700 to 3000 VA
On Line Regulation
-10%,+6%; within Computer Business
Equipment Manufacturers Association’s
Guidelines (+10%;-15% using extended
range)
On Battery Regulation
<±5% RMS
Voltage Wave Shape
Sine wave,3% THD (T700 and T700h
models:quasi-sine wave)
No Load Sleep Mode (Battery Mode)
Outputs are turned off if <5% load is
detected (selectable),except T700
Interconnecting Cords (high voltage
models)
Rack models: 6 ea.IEC-320 (10 A)
Tower models:2 ea. IEC-320 (10 A)
Backup Time
15 minutes @ typical load
Battery Charging
<3 hrs.to 90% usable capacity
Battery Type
Sealed,maintenance-free lead-acid;starved
electrolyte
Start-On-Battery
Startup with UPS batteries in absence of
utility power
Compaq UPS Technical Specifications
Indicators and Controls
Serial Communication
Intelligent serial communication to provide
alarms with history,measured parameters,
self-test,and many other features
REPO Port
Remote Emergency Power Off; allows for
shutdown of UPS (rack models only)
Environmental and Safety
Dimensions and Weight
See Model Selection Guide
Operating Temp
0°C - 40°C (32°F - 104°F) UL tested at
25°C (77°F)
Storage Temp
-20°C - 60°C (-4°F -140°F)
Relative Humidity
5 to 95% non-condensing
Operating Altitude
Up to 3,000 meters above sea level
EMC Markings
FCC;low voltage models also VCCI; high
voltage models also CE
Emissions
FCC Class B 700,1000, 1500VA models;
FCC Class A 2000, 2400,3000VA models;
high voltage models also CISPR Class A,
EN50091-2,EN55022, and IEC6100-3-2
Surge Suppression
Manufactured with surge suppressors that
meet UL 1449
Safety Certifications
UL 1778,CSA 22.2, No.107.1; high volt-
age models also EN50091-1 and IEC60950
Safety Markings
UL and CSA;120 volt models also NOM*;
high voltage models also CE,VDE, S*, FI*,
N*,and D* (except models T700 and T700h)
Immunity
EN50091-2,IEC6100-4-2,3,4,5 and ANSI
C62.41 Cat B (formerly IEEE 587)
REPO Port
Meets NEC code 645-11 intent and UL
requirements