Specifications

21
Which Compaq UPS is Right for You?
Determining the Required
UPS Power Rating
The table below shows which UPS models
can be used with the various Compaq
server and storage system models.This
will vary with actual configurations,
type of peripherals also protected by
the UPS,and amount of backup time
required.The VA values shown on the
adjacent chart are maximum values.
For configurations involving multiple
servers and/or additional critical stor-
age/option products,simply add up the
total VA of the equipment that will be
plugged into the UPS and select the
UPS model with a VA rating higher than
the equipment load.To allow for future
system growth,a good rule of thumb is
that the computer load should be about
60% - 80% of the UPS VA capacity.
300 VA 19 49 79 92 162 67 187
350 VA 16 30 67 79 139 57 160
400 VA 14 26 59 69 122 50 140
450 VA 12 23 43 58 108 36 124
500 VA 9 21 38 51 97 32 112
600 VA 7 16 32 36 81 27 93
700 VA 5 14 27 30 62 23 80
800 VA 12 24 26 54 20 56
900 VA 9 17 23 48 15 50
1000 VA 8 16 20 43 13 45
1200 VA 13 14 36 11 38
1400 VA 10 12 24 8 32
1500 VA 9 10 23 7 30
1800 VA 8 19 21
2000 VA 7 16 19
2200 VA 14 17
2400 VA 13 14
3000 VA 11
*VA loads are estimates;size UPS according to total actual equipment configurations VA load.
**Includes external battery cabinet.
Estimated Backup Time in Minutes
Load* T700 Series T1000
Load T700 Series T1000 Series T1500 Series T2000 Series**
T2400 Series** R1500 Series R3000 Series
Volts x Amps = VA per
device
If only Watts are given:
Watts x 1.35 = VA
VA/1000 = KVA
Compaq VA Redundant
Products Rating Power Supply
14- or 15- inch Compaq Monitor
1
112 N/A
4/8 Port Rack Switch
1
117 N/A
SCSI Storage Expander
1
235 N/A
ProLiant 850, 850R
1
270 N/A
ProSignia 200
1
280 N/A
ProSignia VS or ProSignia 300
1
285 N/A
ProLiant 800
1
324 N/A
CPW 5000
1
324 N/A
ProSignia 500
1
345 N/A
CPW 5100
1
378 N/A
ProLiant 1200
1
378 N/A
CPW 6000, 8000
1
439 N/A
ProLiant 1600,1600R
1
439 N/A
ProLiant Storage System
1
465 N/A
ProLiant 2500, 2500R
1
470 N/A
ProLiant 1500, 1500R
1
500 N/A
ProLiant Storage System F1/F2
1
585 N/A
ProLiant 2000, 2000R
2
659 N+1
ProLiant 4500, 5000,4500R, 5000R
2
729 N+1
DLT Array II
1
745 N/A
ProLiant 3000, 5500,6500
2
1013 N+1
ProLiant 6000, 7000
3
2025 2N+1
1
VA Rating is calculated at maximum configuration of the system.
2
VA Rating is calculated based on N+1 maximum configuration.
3
VA Rating is calculated based on 2N+1 maximum configuration.