Operating instructions

STUDER Innotec COMPACT
COMPACT V6.8.0 24/83
Caution: the COMPACT will not limit if an appliance draws more current than
available from the source! This means that the connected generator will be
over-loaded or that the circuit-breaker before the COMPACT will break.
5 Programming
The COMPACT is equipped with a Flash processor fitted out with a Flash
memory, which means that even when it is disconnected from the battery, the
parameters that were programmed for the application remain after a new
connection to the battery.
It is possible to reinitialize (RESET) the COMPACT by pressing simultaneously
on the three push buttons 19/20/21 during at least 2 seconds. A beep will
confirm the RESET. The inverter switches off after this operation. It can be
turned on again after the beep. The programmed parameters will remain.
5.1 Standard setting
The COMPACT is delivered with the following default settings:
Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13
Battery voltage : Low voltage 11.6V / 23.2V / 46.4V
Float Charge 13.5V / 27.0V / 54.0V
End of Charge Voltage 14.4V / 28.8V / 57.6V
Equalization 15.6V / 31.2V / 62.4V
Absorption Time : 2 Hours
Equalizing Time : 20 Minutes
5.2 Reset value (default settings)
To come back to the default settings, press simultaneously on the push buttons
20/21 during at least 2 seconds. A beep will confirm the comeback to the factory
settings. The inverter switches off after this operation. It can be turned on again after
the beep.
5.3 Battery voltages and absorption time
5.3.1 Set the voltage and timing threshold
The programming is done in
accordance with the following
steps:
Push and hold down, the Push
Button 21 (Program) and the
Push Button 19 (Change status)
for minimum 2 seconds
simultaneously.
With the Push Button 20 (select)
select which of the battery level
and of the absorption time have
to be changed.
These four red LED’s show the function set:
Low voltage LED 13 (ON/OFF)
Float charge LED 12 (Batt. Low/high)
Absorption (End of charge) LED 11 (Overload)
Equalization LED 10 (Overtemp.)