Coaxial Data Sheet
This data is provided as a means to determine the number of cables that will fit into a conduit.
Product
Diameter (DOJ) X-Sectional Area Pulling Tension
Inches mm Inches mm Lbs kgf
P3412 0.485 12.32 0.185 119.19 150 68
P3500 0.570 14.48 0.255 164.63 300 136
P3565 0.635 16.13 0.317 204.32 350 159
P3625 0.695 17.65 0.379 244.75 475 215
P3700 0.775 19.69 0.472 304.34 500 227
P3750 0.830 21.08 0.541 349.07 675 306
P3840 0.920 23.37 0.665 428.88 700 318
P3875 0.955 24.26 0.716 462.13 875 397
QR540 0.610 15.49 0.292 188.55 220 100
QR715 0.785 19.94 0.484 312.25 340 154
QR860 0.960 24.38 0.724 466.98 450 204
MC
2
500 0.605 15.37 0.287 185.47 300 136
MC
2
650 0.735 18.67 0.424 273.74 500 227
MC
2
750 0.855 21.72 0.574 370.42 700 318
NOTE: All cables have standard jacket and flooding compound over the aluminum outer conductor.
Specifications subject to change without notice.
8.9 Appendix
Fill Percentage Calculation