User guide
Appendix 8.6
Toneable Conduit Specifications
Conduit Size
CU-Clad
Wire Size
AWG
Outside
Diameter
(inches)
Wall Thickness
(inches)
Nominal
Inner
Diameter
(inches)
Min. Bend
Radius
Unsupported
(inches)
Max.
Pulling
Tension
(lbs.)
Weight
(lb/ft)
3/4" SDR 11 18 1.050 ± 0.005 0.095 ± 0.020 0.84 20 687 0.128
1.00" SDR 13.5 18 1.315 ± 0.007 0.097 ± 0.020 1.101 26 894 0.166
1.25" SDR 13.5 18 1.660 ± 0.008 0.123 ± 0.020 1.394 34 1,425 0.263
1.50" SDR 13.5 18 1.900 ± 0.010 0.141 ± 0.020 1.598 38 1,867 0.344
2.00" SDR 11 18 2.375 ± 0.012 0.216 ± 0.026 1.917 48 3,515 0.642
2.00" SDR 13.5 18 2.375 ± 0.012 0.176 ± 0.021 2.002 48 2,917 0.534
2.00" SCH 40 18 2.375 ± 0.012 0.154 ± 0.020 2.047 48 2,579 0.473