- Fixture/ stud holder for the ceiling closing plate (Fig. 2). There are also two slotted holes (10 mm)
available. If one or both screws are loosened, the stud holder can be moved either up or down.
Fig.2
3.8.6 Completion of all electronic and mechanical adjustments
After the test run has been completed successfully (LED lights up permanently), an exceptional
increase of power input during the movement of the ProFLECT II i will be interpreted as a blockage.
If a blockage is detected when the ProFLECT II i is moving “Up”, the unit will stop immediately and
move to “open” position. If a blockage is detected when the ProFLECT II i is moving “Down”, it will
stop immediately. A blockage will be detected if a force larger than approx. 5 kg is applied.