Testing Procedure
ComfortPro Systems, LLC
8150 N. Lehigh
Morton Grove, IL 60053
Phone (800) 968-8905
Fax: (847) 967-1482
AquaHeat PEX Testing Procedure
General
Every radiant or snow melting system should be tested while all piping is still fully
exposed to insure that there are no leaks in the tubing system. This is a common sense
step in any application of piping. Further, it is a Warranty Requirement for all
AquaHeat PEX installations. If this step is omitted, there is no warranty from the
manufacturer of the tubing.
Timing
The pressure test must be performed after installation of all tubing circuit installations
are completed. The manifold and tubing system should be tested as an assembly.
There is no practical way to pressure test each individual circuit. The shutoff valves on
the manifold will not shut off against an 80 psig differential. If walls or a permanent
installation point for the manifold is not available, a temporary support should be
fabricated. The tubing ends and the manifold location will not change once installed, so
the manifold should be fastened to the temporary support at the correct elevation for the
permanent location.
Air or Water
The tubing system can be tested with either air pressure or hydrostatically with water.
Depending on the climatic conditions, the correct medium should be selected. Once
water is put in a radiant system it is almost impossible to drain it 100%. Unless it is
certain that no freezing temperatures will be experienced before system fill and
activation, air pressure is the safest selection. The automatic air vent that is supplied
with each manifold should be removed during the testing procedure.
Test Procedures
The manifold assembly must be completely isolated from the system piping during
testing. Both the supply and return connections must be available. The 1” return
manifold end should be fitted with a nipple and drain valve. The supply manifold should
be fitted with a nipple and charging valve to introduce and pressurize either the air or
water. A pressure gauge should be fitted to either side of the manifold to monitor
charge and retain pressure in the tubing system. The pressure gauge should be at
least 4” diameter so movement of the indicating needle can be easily read.
Once pressure tight and ready, air or water should be introduced into the system. If air
is used, the system should simply be charged to a pressure of at least 80 psig. If water
is used, the system should be filled and bled through the return manifold drain valve.
Each loop must be bled individually to make certain all air has been remove. Any
residual air left in the tubing will be absorbed into the test water and result in a false
indication of a leak.


