Installation manual
www.fmiproducts.com
125685-01B12
INSTALLATION
Continued
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 11,
are not met, you must have a hood. When
using a hood there are still certain minimum
mantel clearances required. Follow minimum
clearances shown in Figure 7, when using
hood.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
14"
Min.
Combustible
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 7 - Minimum Mantel Clearances
When Using Hood
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the replace, you must install appliance
at least 5" above the combustible ooring
(see Figure 9).
Hearth
5"
Min.
Combustible
Material
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, ap-
pliance must be installed only in a solid-fuel
burning replace with a working ue and con-
structed of noncombustible material.
For Massachusetts Residents Only: Instal-
lation of this gas log set as a vented appliance
in the Commonwealth of Massachusetts re-
quires the damper be permanently removed
or welded in the fully open position.
You may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The replace does not meet the clearance
to combustibles requirements for vent-
free operation.
2. State or local codes do not permit vent-
free operation.
3. You prefer vented operation.
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18"
All minimum
distances are
in inches
Log Sets
24" Models
20"
2
1
/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050
or GA6053)
Top of
Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf