Installation manual

www.desatech.com
111161-01K10

Use the correct gas type (natural or propane/
LP) for your unit. If your gas supply is not cor-
rect, do not install heater. Call dealer where
you bought heater for proper type heater.



-


INSTALLATION AND CLEARANCES
()
WARNING: Maintain the





Side Wall 16" Ceiling: 42"


  
    
24" 17" 13" 28" 21"
30" 17" 13" 34" 24"
* Measured at 13" depth.
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured replace or listed
vent-free rebox.
-

A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
1
/
2
" from the wall. This com-
bustible material must be 4" from the side
of the replace opening (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturers instructions for minimum
clearances to combustible materials.
INSTALLATION
Continued
Figure 4 - Minimum Clearance for
Combustible to Wall
*Minimum 16" from Side Wall
*
Example

Clearances

Note: If using a mantel, proceed to If Using
Mantel, page 11. If not using a mantel, follow
the information below.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up. If noncombustible material is
less than 12", you must install the replace
hood accessory. See Figure 5, page 11, for
minimum clearances.
IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater
with chimney ue damper open. Go to Install-
ing Damper Clamp Accessory for Vented
Operation, page 12.
B. Clearances from top of replace opening
to ceiling should not be less than 42".
NOTICE: Manual control heaters

If so, you must always run heater

    


Installing Damper
Clamp Accessory for Vented
Operation