Design Guide - HZH/HZV Series
HZ Series 60Hz
Engineering Specications – Page 5
Random start on power up mode.
Low voltage protection.
High voltage protection.
Unit shutdown on high or low refrigerant pressures (loss of charge).
Unit shutdown on low water temperature.
Condensate overow electronic protection.
Option to reset unit at thermostat or disconnect.
Automatic intelligent reset. Unit shall automatically reset the unit 5 minutes after trip if the fault has cleared. If a fault
occurs 3 times sequentially without thermostat meeting temperature, then lockout requiring manual reset will occur.
Ability to defeat time delays for servicing.
Light emitting diode (LED) on circuit board to indicate high pressure, low pressure (loss of charge), low voltage, high
voltage, low water/air temperature cut-out, condensate overow, and control voltage status.
The low-pressure (loss of charge) switch shall not be monitored for the rst 120 seconds after a compressor start
command to prevent nuisance safety trips.
24V output to cycle a motorized water valve or other device with compressor contactor.
Unit Performance Sentinel (UPS). The UPS warns when the heat pump is running inefciently.
Water coil low temperature sensing (selectable for water or antifreeze).
Air coil low temperature sensing.
Removable thermostat connector.
Night setback control.
Random start on return from night setback.
Minimized reversing valve operation (Unit control logic shall only switch the reversing valve when cooling is demanded
for the rst time. The reversing valve shall be held in this position until the rst call for heating, ensuring quiet operation
and increased valve life.).
Override temperature control with 2-hour timer for room occupant to override setback temperature at the thermostat.
Dry contact night setback output for digital night setback thermostats.
Ability to work with heat pump (Y, O) or heat/cool (Y, W) type thermostats.
Ability to work with heat pump thermostats using O or B reversing valve control.
Emergency shutdown contacts.
Boilerless system heat control at low loop water temperature.
Ability to allow up to 3 units to be controlled by one thermostat.
Relay to operate an external damper.
Ability to automatically change fan speed from multistage thermostat.
Relay to start system pump.
75 VA control transformer. Control transformer shall have load side short circuit and overload protection via a built in
circuit breaker.
NOTE: Units not providing the 8 safety protections of anti-short cycle, low voltage, high voltage, high refrigerant
pressure, low pressure (loss of charge), air coil low temperature cut-out, water coil low temperature cut-out, and
condensate overow protections will not be accepted.
Note: To achieve full benet of the two-stage compressor and ECM fan, a 2 Heat/2 Cool thermostat (or a 3 Heat/2
Cool thermostat when electric backup heat is required) should be employed.
Digital Night Setback with Pump Restart
The unit will be provided with a Digital Night Setback feature using an accessory relay on the DXM2 controller and an
external, eld-provided time clock. The external time clock will initiate and terminate the night setback period. The
thermostat will have a night setback override feature with a programmable override time period.
An additional accessory relay on the unit DXM2 controller will energize the building loop pump control for the duration of
the override period. (Note: this feature requires additional low voltage wiring. Consult Application Drawings for details.)