User Guide
38
Design Guide - HZH/HZV Series
Blower Performance Data
Standard Unit (ECM)
Airow in CFM with wet coil and clean air lter
Model
Max ESP
(in wg)
Fan Motor
(hp)
Range
Cooling Mode Dehumid Mode Heating Mode
Fan Only
Mode
Stg 2 Stg 1 Stg 2 Stg 1 Stg 2 Stg 1
024 1.0 1/2
Default 700 525 550 425 750 600 350
Maximum 1000 800 800 600 1000 850 1000
Minimum 600 450 550 400 600 450 300
036 0.9 1/2
Default 1050 800 850 650 1100 850 550
Maximum 1500 1100 1200 900 1500 1100 1500
Minimum 900 600 825 550 900 600 450
048 1.0 1
Default 1400 1050 1100 850 1500 1150 700
Maximum 2000 1500 1600 1200 2000 1500 2000
Minimum 1200 900 1100 825 1200 900 600
060 0.7 1
Default 1750 1300 1400 1050 1875 1450 875
Maximum 2300 1900 2000 1500 2300 1900 2300
Minimum 1500 1100 1375 1000 1500 1100 750
070 0.7 1
Default 1900 1450 1650 1250 2000 1650 950
Maximum 2300 2200 2000 1800 2300 2200 2300
Minimum 1800 1350 1650 1250 1800 1350 900
Airow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” berglass lter.
ClimaDry II equipped units are factory set to operate in stage 2 airow.
HZ Series with ClimaDry II
All HZ units have an ECM fan motor. The small amount of
additional pressure drop of the ClimaDry II coil causes the ECM
motor to slightly increase RPM to overcome the added pressure
drop and maintain selected CFM up to the maximum ESP.










