Product Overview
Model 024 036 048 060 070
Compressor (1 Each) Two-Stage Scroll
Factory Charge (HFC-410A)
(oz) [kg]
44 [1.25] 52 [1.47] 69 [1.96] 142 [4.03] 140 [3.97]
ECM Fan Motor & Blower
Fan Motor (hp) [W] 1/2 [373] 1/2 [373] 1 [746] 1 [746] 1 [746]
Blower Wheel Size (dia x w) -
(in) [mm]
9 x 7 [229 x 178] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 10 [279 x 254]
Water Connection Size
FPT (in) 1 1 1 1 1
HWG Connection Size
FPT (in) 1/2 1/2 1/2 1/2 1/2
Coax Volume
Volume (US Gallons) [liters] 0.76 [2.88] 0.92 [3.48] 1.24 [4.69] 1.56 [5.91] 1.56 [5.91]
Vertical Upow/Downow
Air Coil Dimensions (h x w) -
(in) [mm]
28 x 20 [711 x 508] 28 x 25 [711 x 635] 32 x 25 [813 x 635] 36 x 25 [914 x 635] 36 x 25 [914 x 635]
Standard Filter - 1” [25.4mm]
Throwaway, qty (in) [mm]
28 x 24 [711 x 610] 28 x 29.5 [712 x 749] 32 x 29.5 [813 x 749] 36 x 29.5 [914 x 749] 36 x 29.5 [914 x 749]
Weight - Operating, (lbs) [kg] 298 [135] 359 [163] 448 [203] 475 [215] 475 [215]
Weight - Packaged, (lbs) [kg] 308 [140] 369 [167] 458 [208] 485 [220] 485 [220]
Weight-ClimaDry II (lbs) [kg] 38 [17] 41 [19] 44 [20] 49 [22] 49 [22]
Horizontal
Air Coil Dimensions (h x w) -
(in) [mm]
18 x 31 [457 x 787] 20 x 35 [508 x 889] 20 x 40 [508 x 1016] 20 x 45 [508 x 1143] 20 x 45 [508 x 1143]
Standard Filter - 1” [25.4mm]
Throwaway, qty (in) [mm]
2 - 18 x 18 [457 x 457]
1 - 12 x 20 [305 x 508]
1 - 20 x 25 [508 x 635]
1 - 18 x 20 [457 x 508]
1 - 20 x 24 [508 x 610]
2 - 20 x 24 [508 x
610]
2 - 20 x 24 [508 x 610]
Weight - Operating, (lbs) [kg] 298 [135] 359 [163] 448 [203] 475 [215] 475 [215]
Weight - Packaged, (lbs) [kg] 308 [140] 369 [167] 458 [208] 485 [220] 485 [220]
Weight-ClimaDry II (lbs) [kg] 38 [17] 41 [19] 44 [20] 49 [22] 49 [22]
Notes:
All units have TXV expansion device and 1/2” & 3/4” electrical knockouts.
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F
Full Cool 77°F Part
Cool 68°F
Full Heat 32°F Part
Heat 41°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
HZ024 Part 19,200 19.8 23,600 7.0 22,000 34.1 19,000 5.4 20,800 28.0 16,800 5.0
HZ024 Full 25,000 17.4 31,400 6.0 28,500 26.4 25,800 5.1 26,000 19.9 20,200 4.1
HZ036 Part 27,400 20.1 32,600 6.5 30,700 34.4 27,300 5.5 29,700 29.6 23,800 4.8
HZ036 Full 37,700 17.9 45,700 5.8 42,100 26.1 37,900 5.2 39,000 20.3 29,700 4.4
HZ048 Part 36,300 18.8 42,200 6.1 41,800 32.9 34,800 5.0 39,100 27.4 29,800 4.4
HZ048 Full 48,600 16.8 56,700 5.1 55,000 25.3 46,800 4.6 49,600 19.3 36,400 4.0
HZ060 Part 46,300 18.7 54,700 6.0 53,100 32.4 44,000 5.0 51,200 26.7 38,100 4.4
HZ060 Full 61,500 16.2 77,400 5.4 71,500 24.4 63,200 4.8 66,200 18.8 48,700 3.9
HZ070 Part 53,000 16.8 64,600 5.2 60,800 28.6 53,200 4.5 58,100 23.2 46,000 3.9
HZ070 Full 68,300 15.1 85,300 4.8 77,700 22.5 71,400 4.4 71,700 16.9 55,800 3.7
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
Ground Loop Heat Pump ratings based on 15% antifreeze solution
All ratings based upon operation at lower voltage of dual voltage rated models
PHYSICAL DATA
TESTED TO ASHRAE/AHRI/ISO 13256-1 ENGLISH (I-P) UNITS
Due to ongoing product improvements, specications and dimensions are subject to change and
correction without notice or incurring obligations. Determining the application and suitability for use
of any product is the responsibility of the installer. Additionally, the installer is responsible for verifying
dimensional data on the actual product before beginning any installation preparations. All products meet
applicable regulations in effect on date of manufacture; however, certications aren’t necessarily granted
for life of the product. It is the responsibility of the applicant to determine whether a specic model
qualies for third party incentive/rebate programs (Federal, state, utilities, etc.).
SP-1M 3/21 CA-HZ
“This product complies with all California product
labeling laws including, but not limited to, the Safe
Drinking W
ater and Toxic Enforcement Act of 1986,
more commonly known as Proposition 65.”
HZ Series