Install Instructions

IOM - HZH/HZV Series
43
Operating Limits
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where
humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water
temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the
other two factors should be at normal levels to ensure proper unit operation. Extreme variations in temperature and
humidity and/or corrosive water or air will adversely affect unit performance, reliability, and service life. Consult Table
9a for operating limits.
Commissioning Conditions
Consult Table 9b for the particular model. Starting conditions vary depending upon model and are based upon the
following notes:
Notes:
1. Conditions in Table 9b are not normal or continuous operating conditions. Minimum/maximum limits are start-up
conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under
these conditions on a regular basis.
2. Voltage utilization range complies with AHRI Standard 110.
Table 9a: Operating Limits
Operating Limits
TE
Cooling Heating
Air Limits
Min. ambient air, DB
Rated ambient, DB
Max. ambient air, DB
Min. entering air, DB/WB
Rated entering air, DB/WB
Max. entering air, DB/WB
45ºF [7ºC]
80.6ºF [27ºC]
130ºF [54.4ºC]
65/45ºF [18/7ºC]
80.6/66.2ºF [27/19ºC]
100/75ºF [38/24ºC]
39ºF [4ºC]
68ºF [20ºC]
85ºF [29ºC]
50ºF [10ºC]
68ºF [20ºC]
80ºF [27ºC]
Water Limits
Min. entering water
Normal entering water
Max. entering water
*20ºF [-6.7ºC]
50 – 110ºF [10 – 43.3ºC]
120ºF [48.9ºC]
20ºF [-6.7ºC]
30-80ºF [-1.1 – 26.7ºC]
*120ºF [48.9ºC]
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
* = Temperatures shown are for units with vFlow internal pump or modulating valve. For units without a vFlow device the
minimum entering water temperature for cooling is 30°F (-1.1°C) and the maximum for heating is 90°F (32.2°C).
Unit Starting and Operating Conditions
Table 9b: Commissioning Limits
* = Temperatures shown are for units with vFlow internal pump or modulating valve. For units without a vFlow device the
minimum entering water temperature for cooling is 30°F (-1.1°C) and the maximum for heating is 90°F (32.2°C).
Commissioning Limits
TE
Cooling Heating
Air Limits
Min. ambient air, DB
Rated ambient, DB
Max. ambient air, DB
Min. entering air, DB/WB
Rated entering air, DB/WB
Max. entering air, DB/WB
45ºF [7ºC]
80.6ºF [27ºC]
130ºF [54.4ºC]
60/45ºF [16/7ºC]
80.6/66.2ºF [27/19ºC]
100/75ºF [38/24ºC]
39ºF [4ºC]
68ºF [20ºC]
85ºF [29ºC]
50ºF [10ºC]
68ºF [20ºC]
80ºF [27ºC]
Water Limits
Min. entering water
Normal entering water
Max. entering water
*20ºF [-6.7ºC]
50 – 110ºF [10 – 43.3ºC]
120ºF [48.9ºC]
20ºF [-6.7ºC]
30-80ºF [-1.1 – 26.7ºC]
*120ºF [48.9ºC]
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]