Brochure

18
BTUH Ratings: Cooling at 59°F entering water temp; heating at 50°F entering water
temperature.
DMX2 digital controller uses information from
sensors to customize the operation for optimal
efciency. Operational data is displayed in plain
English on communicating thermostat or optional
diagnostic tool. HZ models work for open loop,
closed loop residential applications.
Features two stage compressor, variable speed ow
technology, ECM blower motor.
BTUH Ratings: Cooling at 59°F entering water temperature; heating at 50°F entering water temperature.
Ratings above with WDG air handler matches; ratings vary with MWG coils.
Exceptional efciency with full/part load shifting
and two-stage scroll compressor. Features
micro-processor controls, quiet operation and
performance monitoring system.
Cabinets can be stacked for multi-unit
installations.
GeoLogix
TM
Plus Two Stage Geothermal Heat Pump (Split)
GEOTHERMAL/WATER SOURCE EQUIPMENT
GeoLogix
TM
HZ Series with Two-Way Communicating Controls
208/230-1-60
2 to 6 Tons
HZV upow—shown right; also HZD downow and HZH horizontal available.
Model
Capacity
Modulation Specs for Groundwater Installation EER/COP
HZV/HZD/
HZH024
Full
Part
BTUH: 28,500 cooling/25,800 heating
BTUH: 22,000 cooling/19,000 heating
26.4/5.3
34.1/5.8
HZV/HZD/
HZH036
Full
Part
BTUH: 42,100 cooling/37,900 heating
BTUH: 30,700 cooling/27,300 heating
26.1/5.2
34.4/5.5
HZV/HZD/
HZH048
Full
Part
BTUH: 55,000 cooling/46,800 heating
BTUH: 41,800 cooling/34,800 heating
25.3/4.6
32.9/5.0
HZV/HZD/
HZH060
Full
Part
BTUH: 71,500 cooling/63,200 heating
BTUH: 53,100 cooling/44,000 heating
24.4/4.8
32.4/5.0
HZV/HZD/
HZH070
Full
Part
BTUH: 77,700 cooling/71,400 heating
BTUH: 60,800 cooling/53,200 heating
22.5/4.4
28.6/4.5
Model
Capacity
Modulation Specs for Groundwater Installation EER/COP
HZS024
Full
Part
BTUH: 25,600 cooling/24,000 heating
BTUH: 20,400 cooling/18,700 heating
22.4/4.5
27.8/4.8
HZS036
Full
Part
BTUH: 40,500 cooling/32,700 heating
BTUH: 28,800 cooling/23,700 heating
23.4/4.5
29.7/4.8
HZS048
Full
Part
BTUH: 52,800 cooling/45,900 heating
BTUH: 40,700 cooling/34,300 heating
23.0/4.2
29.4/4.6
HZS060
Full
Part
BTUH: 62,400 cooling/56,600 heating
BTUH: 48,100 cooling/41,700 heating
20.3/4.0
26.0/4.3
Match with MWG multi-position
coils or DG air handlers.
208/230-1-60
2 to 5 Tons