Product Overview

VMH’ Series
Single Zone Ductless Mini-Splits with Inverter Technology
FEATURES
Heat Pump Models
VMH09SD-0* VMH12SD-0* VMH09SD-1* VMH12SD-1* VMH18SD-1* VMH24SD-1* VMH30SC-1 VMH36SC-1
Power Supply 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Cooling Capacity (BTUH) 9,000 12,000 9,000 11,500 17,500 23,000 30,000 36,000
SEER 24.40 23.00 23.50 21.50 21.00 19.00 16.00 14.50
EER 15.00 13.50 14.50 13.00 12.50 12.50 10.00 8.80
HSPF 10.00 10.00 10.00 10.00 9.50 9.00 9.60 9.00
Cooling Amps 5.22 7.74 2.9 4.0 6.5 8.4 14.0 15.7
Dehumidication (Pts/Hr.) 2.11 2.54 2.11 2.54 3.6 5.3 6.3 8.0
Hi Heating Cap. (BTUH) @ 47°F 10,000 12,000 15,602 15,760 16,316 29,345 29,551 32,748
Lo Heating Cap. (BTUH) @ 17°F 6,400 6,400 10,201 12,420 9,424 18,773 17,644 20,880
Heating Amps 6.96 8.7 4.2 4.2 6.7 9.1 11.0 14.0
INDOOR UNIT
Air ow (CFM) 425/350/280 425/350/280 441/382/265
441/382/265
441/382/265 706/559/441 853/765/618 971/842/736 971/842/736
Fan Speeds (Hi/Med/Lo) 3 3 3 3 3 3 3 3
Sound Level (dBa) H-M-L
41/36/29 42/37/31 43/37/31 43/37/31 47/40/31 50/45/40 50/47/43 50/46/42
AIR DIRECTION
Vertical Adjustment Remote Remote Remote Remote Remote Remote Remote Remote
Horizontal (left/right) Manual Manual Manual Manual Manual Manual Manual Manual
Auto Swing Remote Remote Remote Remote Remote Remote Standard Standard
INDICATOR LAMPS
ON/OFF Yes Yes Yes Yes Yes Yes Yes Yes
24 Hr. Timer Yes Yes Yes Yes Yes Yes Yes Yes
Defrost Yes Yes Yes Yes Yes Yes Yes Yes
Temperature Setting Range On Remote: 62°F - 86°F On Remote: 62°F - 88°F
INDOOR UNIT DIMENSIONS
Width (inches) 32
7
/8 32
7
/8 32
7
/8 32
7
/8 39 46
11
/16 56
7
/8 56
7
/8
Height (inches) 11
1
/4 11
1
/4 11 11 12
7
/16 13
7
/16 13
3
/8 13
3
/8
Depth (inches) 7
13
/16 7
13
/16 7
13
/16 7
13
/16 8
9
/16 10
3
/16 10
7
/8 10
7
/8
Net Wt/Shipping Wt (lbs.) 19.2/24.7 19.2/24.7 17.6/22 18.7/24.3 26.5/30.9 40.8/50.7 53/70.6 53/70.6
OUTDOOR UNIT DIMENSIONS
Width (inches) 31
15
/16 31
15
/16 29
15
/16 29
15
/16 33
1
/4 35
7
/16 35
7
/16 39
Height (inches) 22 22 23
1
/4 23
1
/4 27
9
/16 33
7
/8 33
7
/8 38
Depth (inches) 12
1
/4 12
1
/4 11
1
/4 11
1
/4 12
5
/8 12
7
/16 12
7
/16 13
9
/16
Net Wt/Shipping Wt (lbs.) 82.5/88.2 81.6/87.7 73.9/77.2 73.9/77.2 102.5/111.3 130.1/138.9 156.5/165.4 180.8/189.6
ELECTRICAL DATA OUTDOOR UNIT
Main Power Connection Outdoor Unit
Min. Circuit Ampacity 10A 11A 9A 9A 13A 15A 16A 20A
Max. Fuse/HACR Circuit
Breaker
15A 15A 15A 15A 20A 25A 25A 30A
Indoor/Outdoor Connecting
Cable Type
RECOMMENDED: 14 AWG / 4 conductor
600V THHN unshielded stranded bare copper
LINE SETS O.D. (inch)
Liquid Connection (are) (in.) 1/4 1/4 1/4 1/4 1/4 3/8 3/8 3/8
Suction Connection (are) (in.) 3/8 1/2 3/8 1/2 1/2 5/8 5/8 5/8
Max. Line Set Length
1
82 feet 82 feet 82 feet 82 feet 98 feet 98 feet 82 feet 82 feet
Max. Elevation (outdoor)
2
33 feet 33 feet 33 feet 33 feet 66 feet 66 feet 32 feet 32 feet
* Energy Star compliant: 9K, 12K, 18K and 24K
Always follow local, state and national electrical codes
Main power connection is 115V or 208/230V,
depending on model
1
Min. 10 ft. line set recommended
2
Oil traps should be installed every 16.5 to 23 feet (5-7m)
when the outdoor unit is installed above the indoor unit
Warranty—6 years on compressor, 2 years on parts
(Some limitations apply; see printed warranty for details.)
C US