Product Overview

Features
‘Follow’ feature on remote for comfort
Multiple modes: auto, turbo, sleep, fan only
24 Hour timer
Intelligent pre-heat
Wireless remote and wired
thermostat
Self diagnostics
Includes water pump
Features
Auto operation, 24-hour timer
Multiple modes: turbo, sleep, fan only,
dehumidication only
Intelligent pre-heat
Washable air lter
Automatic louver swing
Self diagnostics
Wireless remote and wired wall thermostat
‘Follow’ feature on remote for comfort
Fits 24" x 24" ceiling tile opening
2
3
HIGH WALL MOUNT INDOOR UNITS
FEATURES B-VFH09MB-1 B-VFH12MB-1 B-VFH18MB-1 B-VFH24MB-1
Cooling Capacity BTUH 9,000 12,000 18,000 20,800
Heating Capacity BTUH 9,800 13,000 19,000 21,500
Air Flow Range (CFM) 224 - 430 224 - 453 282 - 588 459-736
Fan Speeds 5 5 5 5
Dehumidication (Pts/Hr) 1.69 2.96 3.80 5.28
Sound Level Range (dBA) 21 to 52 22 to 53 33 to 61 37 to 62
Temperature Setting On Remote: 61°F to 86°F
AIR DIRECTION
Horiz./Vert. Modulating Yes Yes Yes Yes
Four-Way Modulating Yes Yes Yes Yes
DIMENSIONS
Width (inches)
34
1
/16 34
1
/16 40
1
/16 46
3
/8
Height (inches)
11
1
/2 11
1
/2 12
9
/16 12
7
/8
Depth (inches)
8
1
/4 8
1
/4 9 10
3
/8
Net Wt/Shipping Wt (lbs)
24.25/30.9 24.25/30.9 30.9/41.9 39.7/48.5
Liquid-Suction (are)**
1/4” - 1/2” 1/4” - 1/2” 1/4” - 1/2” 3/8” - 5/8”
CEILING CASSETTES
FEATURES B-VFH12CA-1 B-VFH18CA-1 B-VFH24CA-1
Cooling Capacity BTUH
12,000 14,400 22,800
Heating Capacity BTUH
13,000 16,000 27,400
Air Flow Range (CFM)
265-294-353 265-294-353 500-559-694
Fan Speeds
4 4 3
Dehumidication (Pts/Hr)
2.96 3.80 5.28
Sound Level Range (dBA)
42/44/46 42/44/46 35/37/39
Temperature Setting
On Remote or Wired Wall Thermostat: 61°F to 86°F
AIR DIRECTION
Horiz./Vert. Modulating
No No No
Four-Way Modulating
Yes Yes Yes
DIMENSIONS
Width (inches)
22
7
/16 22
7
/16 33
1
/16
Length (inches)
22
7
/16 22
7
/16 33
1
/16
Height (inches)
9
1
/16 9
1
/16 9
7
/16
Net Wt/Shipping Wt (lbs)
39.6/ 50.7 39.6/ 50.7 61.7/ 77.2
Decorative Cover Panel
Panel Dimensions (inches)
Panel Part#: C-VFH1218CA
25
5
/8 x 25
5
/8 x 2
Panel Part#: C-VFH24CA
33
1
/16 x 33
1
/16 x 2
3
/8
Liquid-Suction (are)**
1/4” - 3/8” 1/4” - 1/2” 3/8” - 5/8”
Wired thermostat
You can see how one outdoor condenser is used in conjunction with
multiple indoor air handlers in a single structure. Air handlers can be
installed up to 82' (depending on model) from the condenser, so you
can place the condenser in the best location for your landscaping.
A hole approximately 3" in diameter is drilled through the exterior
wall to accommodate the lines carrying refrigerant. Also, a
communication wire runs between each indoor unit and the
condenser, and a drain line from each indoor unit carries condensate
away. Power is supplied by the outdoor unit so there are no cords or
plugs visible on the interior.
Features
‘Follow’ feature on remote for comfort
Multiple modes: auto, turbo, sleep, fan only
24 Hour timer
Intelligent pre-heat
Automatic louver swing
Wireless remote
Silver ion ltration
Self diagnostics
FLOOR/CEILING MOUNT INDOOR UNITS
FEATURES B-VFH09UA-1 B-VFH12UA-1 B-VFH18UA-1 B-VFH24UA-1
Cooling Capacity BTUH 8,500 11,900 17,000 22,800
Heating Capacity BTUH 9,500 13,100 18,700 27,400
Air Flow Range (CFM) 383/324/265 383/324/265 559/412/294 736/530/412
Fan Speeds 4 4 4 3
Dehumidication (Pts/Hr) 1.69 2.96 3.80 5.28
Sound Level Range (dBA) 36 to 50 36 to 50 40 to 55 44 to 58
Temperature Setting
On Remote: 61°F - 86°F
DIMENSIONS
Width (inches)
48 48 48 48
Height (inches)
27
5
/16 27
5
/16 27
5
/16 27
5
/16
Depth (inches)
8
7
/8 8
7
/8 8
7
/8 8
7
/8
Net Wt/Shipping Wt (lbs)
88.2/110.2 88.2/110.2 88.2/110.2 99.2/119.1
Liquid-Suction (are)**
1/4” - 3/8”
1/4” - 3/8”
1/4” - 1/2”
3/8” - 5/8”
DUCTED INDOOR UNITS
FEATURES B-VFH09DA-1 B-VFH12DA-1 B-VFH18DA-1 B-VFH21DA-1 B-VFH24DA-1
Cooling Capacity BTUH 8,500 11,900 15,300 20,400 23,800
Heating Capacity BTUH 9,500 13,100 18,700 22,600 27,400
Air Flow Range (CFM) 265/177/147 324/235/177 412/353/294 589/441/324 589/441/324
Fan Speeds 3 3 3 3 3
Dehumidication (Pts/Hr) 1.69 2.96 3.80 4.23 5.28
Sound Level Range (dBA) 31 to 47 32 to 49 33 to 51 34 to 52 34 to 52
Temperature Setting
On Remote: 61°F - 86°F
DIMENSIONS
Width (inches)
27
9
/16 27
9
/16 35
7
/16 43
5
/16 43
5
/16
Height (inches)
7
7
/8 7
7
/8 7
7
/8 7
7
/8 7
7
/8
Depth (inches)
24
3
/16 24
3
/16 24
3
/16 24
3
/16 24
3
/16
Net Wt/Shipping Wt (lbs)
48.5/59.5 50.7/63.9 59.5/79.4 68.3/90.4 68.3/90.4
Liquid-Suction (are)**
1/4” - 3/8”
1/4” - 3/8”
1/4” - 1/2”
3/8” - 5/8” 3/8” - 5/8”
FLOOR MOUNT INDOOR UNITS
FEATURES B-VFH09FA-1 B-VFH12FA-1 B-VFH18FA-1
Cooling Capacity BTUH
9,000 12,000 18,000
Heating Capacity BTUH
9,500 13,000 19,800
Air Flow Range (CFM)
383 - 188 441 - 206 494 - 241
Fan Speeds
5 5 5
Dehumidication (Pts/Hr)
1.69 2.96 3.80
Sound Level Range (dBA)
25 to 50 27 to 53 33 to 58
Temperature Setting
On Remote or Wired Wall Thermostat: 61°F to 86°F
AIR DIRECTION
Vertical Modulating Yes Yes Yes
DIMENSIONS
Width (inches)
27
9
/16 27
9
/16 27
9
/16
Height (inches)
23
5
/8 23
5
/8 23
5
/8
Depth (inches)
8
7
/16 8
7
/16 8
7
/16
Net Wt/Shipping Wt (lbs)
24.25/30.9 24.25/30.9 24.25/30.9
Liquid-Suction (are)**
1/4” - 3/8”
1/4” - 3/8”
1/4” - 1/2”
Low prole
cabinet is less
than 9" deep
Features
Auto operation
Multiple modes: turbo, sleep, fan only,
dehumidication only, 24 Hour timer
‘Follow’ feature on remote
Energy saver function
Intelligent pre-heat
Self diagnosis
Features
‘Follow’ feature on remote
Multiple modes: auto, turbo, sleep, fan only,
dehumidify only, 24 Hour timer
Intelligent pre-heat
Self-diagnosis
4
OUTDOOR UNITS
FEATURES A-VFH18DB-1 A-VFH24TB-1 A-VFH30QB-1 A-VFH36QB-1 A-VFH42PB-1
Power Supply 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
System Cooling Cap. (BTUH) 18,000 24,000 29,000 34,000 39,000
Min./Max. Cooling Cap. (BTUH)
7,000/21,000 7,500/33,000 8190/33,400 8,900/35,800 8,900/40,950
SEER/EER
22.00/12.50 21.00/12.50 21.00/12.50 21.00/12.48 21.00/10.43
HSPF 10.5 10.5 10.5 10.5 10.2
High Heating (BTUH) @ 47°F 19,000 29,500 32,000 41,000 45,000
Low Heating (BTUH) @ 17°F 15,600 19,860 22,500 28,700 30,000
Min./Max. Heating Cap. (BTUH)
8,530/22,600 7,500/35,000 8,200/32,400 8,871/44,356 8,871/46,062
Sound Pressure (dBA) 56 59 59 61 61
OUTDOOR UNIT DIMENSIONS
Width (inches) 37 5/8 38 1/2 38 1/2 42 7/8 42 7/8
Height (inches) 27 1/2 31 1/8 31 1/8 43 3/8 43 3/8
Depth (inches) 15 5/8 16 7/8 16 7/8 17 3/8 17 3/8
Net Wt/Shipping Wt (lbs.) 115/125 153/164 145/154 198/216 198/216
ELECTRICAL DATA OUTDOOR UNIT*
Main Power Connection Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit
Min. Circuit Ampacity 15A 20A 26A 28A 29A
Max. Fuse/HACR Circuit Breaker 25A 30A 30A 35A 40A
LINE SET LENGTHS**
Maximum Line Set Length
1
33 feet 65 feet 82 feet 82 feet 82 feet
Max. Total Length All Zones
65 feet
196 feet 229 feet 246 feet 246 feet
Maximum Elevation (outdoor)
2
32 feet 32 feet 49 feet 49 feet 49 feet
* Always follow local, state and national
electrical codes. Main power connection
is 208-230V.
**See the IOM regarding various adapters
and ttings which may be included with
outdoor and/or indoor models for making
connections.
Recommended Indoor/Outdoor Connecting
Cable (SJOW)— 14 AWG / 4 conductor
600V THHN unshielded stranded bare copper,
not to exceed 98 feet between indoor and
outdoor units.
1
For single indoor unit installation; min. 10 ft.
line set length recommended.
2
Oil traps should be installed every 16.5 to 23
feet (5-7m) when the outdoor unit is installed
above the indoor unit.
NOTE: Maximum line set length varies based
on number of indoor units installed. See
IOM for details.
Mix and match indoor units up to
the maximum BTUHs allowed for
each system—see chart for possible
combinations.
Order outdoor and indoor units
separately:
A” indicates outdoor unit and “B”
indicates indoor units.
C US
Ambient Operating
Temperature Range:
0° - 118.5° F (cooling) (all models);
-4° - 75° F (heating) (18DB-24TB)
-4° - 86° F (heating) (30QB-42PB)
The inverter on a mini-split is like
the cruise control on a vehicle.
The inverter-driven compressor
automatically adjusts its speed to
quickly reach and then maintain the
set point. When maximum capacity
is not needed, the compressor
speed decreases–and with it the
power output also decreases,
resulting in improved energy
efciency. Once the set point is
reached, the system “cruises
along,” keeping the temperature
constant, but responding if the
demand changes.
• Reaches the desired
temperature quickly
• Provides precise temperature
control and continuous
dehumidication (cooling mode)
• Extends component life by
eliminating on-off cycling
• Operates at ultra-quiet level
• Saves energy by matching the
compressor speed to the
demand; rated at 16 SEER and
up to 10.2 EER
• Delivers extra heating capacity
even at low ambient temperatures
Advantages of
Inverter Technology
Wired thermostat
Low
prole
cabinet
Actual performance will vary based on the application,
including the size(s) and mix of indoor units installed.