3.2 UPS Personalization
WARNING Before changing items from Tables, 3-1, 3-2, 3-3, and 3-4, the UPS system
must be turned OFF.
IMPORTANT If specific settings are required, it is recommended to enter the UPS
personalization mode at this stage.
It is possible to enter this mode through the front panel buttons or the
Solution-Pac 2 software for Windows included in the MGE Office Protection Systems
Solution-Pac 2 CD-ROM.
3.2.1 Accessing personalization with front panel buttons
Press "scroll down" and "scroll up" function buttons together for more than 3 seconds.
Press the function button placed under the “ENT” word to enter the set up mode and follow the LCD
messages using the buttons now defined as select keys. See Tables: 3-1, 3-2, 3-3, and 3-4 for settings.
Figure 3-2: Control Panel with scroll up and down buttons.
OFF
ON
21 22
UPS SET UP
EXIT ENT
22
2221
EX 5/7/11 RT Systems
Operation3 — 2 86-86000-00 B01