Specifications
FX II System Installation and Maintenance 
Printed in the USA  Page 7  GCA39-823 Rev 1, Issue 9/01 
•  Make the ground connection with #6 or larger insulated, solid copper grounding wire. 
Keep the ground wire separate from the three-wire AC line cord, do not splice it, and keep it 
as short as possible. 
•  Be sure that all of the ground connections are visible for inspection and maintenance. Tag all 
of the ground connections with a sign that reads: Do Not Remove or Disconnect. 
•  The picture below shows the location of the frame ground on the FX II system. 
•  Effective grounding requires that you connect the frame ground to a good earth ground. A 
good earth ground is one such as the ground bus in the premises’ AC power panel or a public 
metallic cold water pipe at a point immediately at its entrance to the premises and ahead of 
any meters, pumps, or insulating sections that have been added for vibration reduction. Avoid 
using the premises’ structural steel frame as it may not be at earth ground potential. 
•  The impedance of the wiring between the system and the earth ground must not exceed 0.25 
ohms and the impedance between the earth ground and the power company’s reference 
standard ground must not exceed 5 ohms. Use an acceptable low impedance measuring 
device to measure the impedance of these paths. The #6 or larger wire size will minimize the 
wiring impedance; however, if the impedance between earth ground and the power 
company’s standard reference ground exceeds 5 ohms, contact the local power company. The 
ground path must always be of sufficient current-carrying capacity to prevent a build up of 
voltages that may result in circuit noise, hazard to personnel, or equipment damage. 










