Specifications
DX-80 INSTALLATION AND MAINTENANCE MANUAL
P7290 IMM 1-14
Specifications
Current draw:
Use this chart to calculate the Amphour requirements of the DX-80 system based upon its configuration.
This information is typically used to apply UPS battery requirements.
Component Current Draw
(Amps)
@ 117 VAC
Quantity Extended
Total Amps
KSU1 (7201) 0.18A 1 0.18A
KSU2 (7202) 0.17A 1 max.
COM4 (7210) 0.02A 2 max.
DPM8 (7220) 0.01A 4 max.
APM4 (7230) 0.08A 3 max.
MDM (7249) 0.01A 1 max.
AAM (7240) 0.01A 1 max.
PC-8 (7243) 0.015A 1 max.
FL-4 (7241) 0.02A 1 max.
FL3HR (7241E) 0.01A 1 max.
DET (7260-00) 0.016A 48 max.
DSS (7266-00) 0.016A 12 max.
Station wire:
per DET, DSS, and IST
0.02A every 100 ft. of
24AWG
?
Multiply the unit times the quantity installed in the subject application (site) and
add the right column for the total current draw (Amps) @ 117VAC for this
site……