User guide

15
TB1
HTR2
J101
J50
J57
J25
J32
J52
J51
F6, T30A 480V
J47
1
2
3
4
W1
Balboa
BALBOA INSTRUMENTS, INC.
GS500Z
COPYRIGHT 2007
MADE IN U.S.A.
P/N 22015_B
Pb
IMPORTANT!
Remember, high voltage is still accessible in the house
breaker box even though you have turned off the spa breaker.
Keep in mind that a majority of R.C.D. tripping
problems can be attributed to incorrect wiring.
R.C.D. troubleshooting usually finds the problem.
RCD LINE-IN WIRING CHECK
V>ÌiÊÌiÊ«À«iÀÊVÀVÕÌÊLÀi>iÀÊ>`ÊÌÕÀÊÌÊvv°
,iÛiÊÌiÊVÛiÀÊvÀÊÌiÊÕÃiÊLÀi>iÀÊLݰÊiV
the main service amperage rating to the breaker box.
ÀÊÌiÊVÀVÕÌÊLÀi>]ÊV>ÌiÊÌiÊLÀÜÊ>`ÊÜÀiÊ>`Ê
the blue neutral wire.
ÀÊÌiÊ,°°°ÊiÕÌÀ>ÊL>À]ÊV>ÌiÊÌiÊLÕiÊ>`ÊiÕÌÀ>]Ê
and the green ground wire.
iÊÃÕÀiÊÌiÀiÊ>ÀiÊÊÌiÀÊ>««>ViÃÊÊÌiÊë>Ê
circuit. If there are, service must be re-wired to supply the
spa only.
>iÊÃÕÀiÊ>ÊÌÀiiÊÜÀiÃÊiÝÌÊÌiÊÕÃiÊLÀi>iÀÊLÝÊ
via conduit, routed to the R.C.D. breaker box. The brown
should be connected to the R.C.D. line-in. The blue load
neutral connects to the neutral in.
RCD LINE-OUT WIRING CHECK FOR 230 V
DEDICATED SYSTEM
The brown wire should connect to load out, the blue wire
from neutral out. All wires will exit the box via conduit
routed to the spa control system.
Once you have found all wiring correctly installed, begin
to check for proper voltage. If Correct Wiring is Verified,
check to see if the proper RCD is installed.
Check the label in the system box near TB1 to determine
the maximum amperage draw for the system.
Be sure the R.C.D. is rated for more amperage than the
system will draw.
For a 230 V dedicated system, a 2-pole or 4-pole R.C.D.
with no load neutral is acceptable.
For a detailed wiring checklist, please review the previ-
ous segment of this manual on proper R.C.D. wiring or
the R.C.D. manufacturer’s instructions.
If the wiring is correct and the R.C.D. will not reset, then
unplug the pump and try to reset the R.C.D.
If the R.C.D. trips again, then unplug the blower and
push the reset button. If the R.C.D. continues to trip,
then do the same procedure for the ozone generator.
If the R.C.D. stops tripping after you unplugged one
of the spas components, turn off the power to the
spa then plug in each component except the one that
tripped the R.C.D.
Power up the system. If the R.C.D. no longer trips, then
you have correctly identified the problem.
Repair or replace the component as instructed by the
spa manufacturer.
If you have unplugged all of the spas components and
the R.C.D. still doesnt reset, then the problem is most
likely a ground fault in the heater.
Disconnect the heater, and test.
Wiring Check for RCD and Service Disconnect