User manual

Code Mercenaries
3
LL
LL
EE
EE
DD
DD
--
--
WW
WW
aa
aa
rr
rr
rr
rr
ii
ii
oo
oo
rr
rr
00
00
77
77
4. Implemented DALI commands
LED-Warrior07 implements all
IEC62386-102:2009 commands.
It also implements the relevant commands for type
6 control gear according to IEC62386-207:2009.
Since LED-Warrior07 can not measure the lamp
current, power, or temperature the following
commands have no effect:
Command 224: Reference System Power
Command 225: Enable Current Protector
Command 226: Disable Current Protector
Due to the corresponding functions not being
implemented the following commands always
return a negative answer:
Command 241: Query Failure Status
Command 242: Query Short Circuit
Command 243: Query Open Circuit
Command 244: Query Load Decrease
Command 245: Query Load Increase
Command 246: Query Current Protector Active
Command 247: Query Thermal Shut Down
Command 248: Query Thermal Overload
Command 249: Query Reference Running
Command 250: Query Ref Measurement Fail
Command 251: Query Current Protector Enabled
Command 237: Query Gear Type
Returns DC supply possible, all other flags
negative (=0)
Command 239: Query Possible Operating Modes
Returns PWM possible, all other flags negative
(=0) since the actual implementation of the driver
stage is unknown to the LW07.
Command 240: Query Features
Returns zero flags for all features, except physical
selection, which is supported via the /Select input.
4.1 DALI memory banks
LED-Warrior07 implements DALI memory banks
0 and 1. Both banks use the default length with no
vendor or OEM specific additional information.
Bank 1 can be written by the OEM as defined by
the DALI standard.
V1.1.1 April 22nd 2015