Technical data
40 • XM670K-XM679K I&O Manual 026-1218 Rev 0 19-DEC-2012
23 Default Setting Values
Label Value Menu Description Range
SEt 2.0 - - - Setpoint LS - US
REGULATION
Hy 2.0 Pr1 Differential
[0.1°C to 25.5°C]
[1°F to 45°F]
Int 150 Pr1
Integral time for room temperature
regulation
0 to 255 s
CrE n Pr1 Continuous regulation activation n(0) – Y(1)
LS -30 Pr2 Minimum setpoint
[-55.0°C to SET]
[-67°F to SET]
US 20 Pr2 Maximum setpoint
[SET to 150.0°C]
[SET to 302°F]
odS 0 Pr1 Outputs activation delay at start up 0 to 255 (min.)
AC 0 Pr1 Anti-short cycle delay 0 to 60 (min.)
CCt 0.0 Pr2 Continuous cycle duration 0 to 24.0(144)(hour.10min)
CCS 2.0 Pr2 Continuous cycle setpoint
[-55.0°C to 150.0°C]
[-67°F to 302°F]
Con 15 Pr2 Compressor ON time with faulty probe 0 to 255 (min.)
CoF 30 Pr2 Compressor OFF time with faulty probe 0 to 255 (min.)
CF °C Pr2 Measurement unit: Celsius, Fahrenheit °C(0) - °F(1)
PrU rE Pr2 Pressure Mode rE(0) - Ab(1)
PMU bAr Pr2 Pressure measurement unit bAr(0) – PSI(1) - MPA(2)
PMd PrE Pr2
Pressure displaying mode: temperature
or pressure
tEM(0) - PrE(1)
rES dE Pr2 Resolution (only °C): decimal, integer dE(0) - in(1)
Lod P1 Pr2 Local display: default display
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5) - P6(6) – tEr(7) - dEF(8)
rEd P1 Pr2 Remote display: default display
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5) - P6(6) – tEr(7) - dEF(8)
dLy 0 Pr1 Display delay 0 to 24.0(144) (Min.10s)
rPA P1 Pr1 Regulation probe A
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5)
rPb nP Pr1 Regulation probe B
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5)
rPE 100 Pr1
Virtual probe percentage (room
temperature)
0 to 100 (100=rPA, 0=rPb)
ELECTRONIC EXPANSION VALVE
Fty 404 Pr1 Kind of gas
R22(0) - 134(1) - 404(2) - 407(3) -
410(4) - 507(5) - CO2(6)
SSH 8.0 Pr1 Superheat setpoint
[0.1°C to 25.5°C]
[1°F to 45°F]
CyP 6 Pr1 Cycle Period 1 to 15 s
Table 23-1 - Default Setting Values