Technical data

EE Alarm Alarm Signals • 25
15.1.EE Alarm
The controllers are provided with an internal
check for data integrity. Alarm EE flashes when a
failure in the memory data occurs. In such cases, the
alarm output is enabled.
15.2.Alarm Recovery
Probe alarms, P1 (probe1 faulty), P2, P3, P4, P5,
and P6 automatically stop 10 seconds after the probe
restarts normal operation. Check connections before
replacing the probe. Temperature alarms, HA, LA,
HAd, LAd, HAF, and LAF automatically stop as
soon as the thermostat temperature returns to normal
values or when the defrost starts. External alarms
EAL and bAL stop as soon as the external digital in-
put is disabled.