Technical data
Auxiliary Output Parameters List • 19
LSd
Remote probe display: this parameter states if the section has to display the local probe value or the value
coming from another section: y= the displayed value is the one coming from another section (which has
parameter LdS = y); n= the displayed value is the local probe one.
LPP
Remote pressure probe: n= the value of pressure probe is read from local probe; Y= the value of pressure
probe is sent via LAN.
StM
Solenoid activation via LAN: n= not used; Y= a generic cooling requests from LAN activate the solenoid
valve connected to compressor relay.
PROBE CONFIGURATION
P1C Probe 1 configuration: (nP - Ptc - ntc - PtM) nP= not present; PtC= Ptc; ntc= Ptc; PtM= Pt1000
Ot Probe 1 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the thermostat probe.
P2C Probe 2 configuration: (nP - Ptc - ntc - PtM) nP= not present; PtC= Ptc; ntc= Ptc; PtM= Pt1000
OE Probe 2 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offsets of the evaporator probe.
P3C Probe 3 configuration: (nP - Ptc - ntc - PtM) nP= not present; PtC= Ptc; ntc= Ptc; PtM= Pt1000
o3 Probe 3 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the probe 3.
P4C Probe 4 configuration: (nP - Ptc - ntc - PtM) nP= not present; PtC= Ptc; ntc= Ptc; PtM= Pt1000
o4 Probe 4 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the probe 4.
P5C
Probe 5 configuration: (nP - Ptc - ntc - PtM - 420 - 5Vr) nP= not present; PtM= Pt1000; 420= 4 to 20mA;
5Vr= 0 to 5V ratiometric; (Only XM679K)
o5
Probe 5 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the probe 5. (Only
XM679K)
P6C
Probe 6 configuration: (nP - Ptc - ntc - PtM) nP= not present; PtC= Ptc; ntc= Ptc; PtM= Pt1000; (Only
XM679K)
o6
Probe 6 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the probe 6. (Only
XM679K)
SERVICE - READ ONLY
CLt Cooling time percentage: it shows the effective cooling time calculated by XM600 during regulation
tMd Time to next defrost: it shows time before the next defrost if interval defrost is selected
LSn L.A.N. section number (1 to 5) Shows the number of sections available in the L.A.N.
Lan
L.A.N. serial address (1 to LSn) Identifies the device address inside local network of multiplexed cabinet
controller.
Adr
RS485 serial address (1 to 247): Identifies the device address when connected to a MODBUS compatible
monitoring system.
Rel Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map.
Pr2 Access to the protected parameter list (read only)
Table 9-1 - XM670K to XM679K Parameters List