Technical data

18 • XM670K-XM679K I&O Manual 026-1218 Rev 0 19-DEC-2012
Hd1 First weekly holiday (Sun to nu) Set the first day of the week that follows the holiday times.
Hd2 Second weekly holiday (Sun to nu) Set the second day of the week that follows the holiday times.
Hd3 Third weekly holiday (Sun to nu) Set the third day of the week that follows the holiday times.
ILE
Energy Saving cycle start during workdays: (0 to 23h 50 min.) During the Energy Saving cycle, the setpoint
is increased by the value in HES so that the operation setpoint is SET + HES.
dLE
Energy Saving cycle length during workdays: (0 to 24h 00 min.) Sets the duration of the Energy Saving cycle
on workdays.
ISE Energy Saving cycle start on holidays. (0 to 23h 50 min.)
dSE Energy Saving cycle length on holidays (0 to 24h 00 min.)
HES
Temperature increase during the Energy Saving cycle (-30 to 30°C / -54 to 54°F) sets the increasing value of
the setpoint during the Energy Saving cycle.
Ld1 to
Ld6
Workday defrost start (0 to 23h 50 min.) These parameters set the beginning of the eight programmable
defrost cycles during workdays. Ex. When Ld2 = 12.4 the second defrost starts at 12.40 during workdays.
Sd1 to
Sd6
Holiday defrost start (0 to 23h 50 min.) These parameters set the beginning of the eight programmable defrost
cycles on holidays. Ex. When Sd2 = 3.4 the second defrost starts at 3.40 on holidays.
ENERGY SAVING
ESP Energy saving probe selection: (nP - P1 - P2 - P3 - P4 - P5 - tEr).
HES
Temperature increase during the Energy Saving cycle: (-30 to 30°C / -54 to 54°F) sets the increasing value
of the setpoint during the Energy Saving cycle.
PEL
Energy saving activation when light is switched off: (n to Y) n= function disabled; Y= energy saving is
activated when the light is switched off and vice versa
LAN MANAGEMENT
LMd
Defrost synchronization: y= the section send a command to start defrost to other controllers, n= the section
don't send a global defrost command
dEM Type of end defrost: n= the of the LAN defrost are independent; y= the end of the defrost are synchronized;
LSP
L.A.N. set-point synchronization: y= the section set-point, when modified, is updated to the same value on
all the other sections; n= the set-point value is modified only in the local section
LdS
L.A.N. display synchronization: y= the value displayed by the section is sent to all the other sections; n= the
set-point value is modified only in the local section
LOF
L.A.N. On/Off synchronization this parameter states if the On/Off command of the section will act on all the
other ones too: y= the On/Off command is sent to all the other sections; n= the On/Off command acts only in
the local section
LLi
L.A.N. light synchronization this parameter states if the light command of the section will act on all the other
ones too: y= the light command is sent to all the other sections; n= the light command acts only in the local
section
LAU
L.A.N. AUX output synchronization this parameter states if the AUX command of the section will act on all
the other ones too: y= the light command is sent to all the other sections; n= the light command acts only in
the local section
LES
L.A.N. energy saving synchronization this parameter states if the energy saving command of the section will
act on all the other ones too: y= the Energy Saving command is sent to all the other sections; n= the Energy
Saving command acts only in the local section
Table 9-1 - XM670K to XM679K Parameters List