MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN
POINT
ENTR Y
TRIM Sensor Calibration (CCN TRIM --- see
Maintenance Display)
SPT.C Space Temp Calibration ---30 to 130 °F
SPT.T Space Temp Trim --- 30 to 30 ^F 0
SAT.C Supply Air Temp Calib. --- 30 t o 130 °F
SAT.T Supply Air Temp Trim --- 30 to 30 ^F 0
RAT.C Ret urn Air Temp Calib. ---30 to 130 °F
RAT.T Return Air Temp Trim ---30 to 30 ^F 0
CCN CCN Configuration CCN CONFIGURA-
TION
CCN.A CCN Element Number 1 t o 239 1 48_50_LC CCNADD
CCN.B CCN Bus Number 0 to 239 0 CCNBUS
BAUD CCN Baud Rate 1=2400
2=4800
3=9600
4=19200
5=38400
3 CCNBAUDD
BROD CCN Broadcast Config. BRODEFS
B.TIM CCN Time/Date Broadcast No/Yes No CCNBC
B.OAT CCN OAT Broadcast No/Yes No OAT BC
B.GS Global Schedule Broadcst No/Y es No GSB C
B.ACK CCN Broadcast Ack’er No/Yes No CCNBCACK
SCH.O CCN Schedule Overrides SCHEDOVR
SCH.N Schedule Number 0 = Always Occupied
1 --- 6 4 = Lo c a l Sch e d -
ule
65--- 99 = Global
Schedule
0 SCHED-
NUM
HOL.G Accept Global Holidays No/Y es No HOL I D AYT
OV.TL Override Time Limit 0to4 hours 4 OTL
OV.EX Timed Override Hours 0to4 hours --- OVR_EXT
OV.SP SPT Override Enabled No/Yes Yes TIMEOVER
LDSH CCN LOADSHED CONFIG. LOADSHED
S.GRP Loadshed Group Number 0to16 0 SHED_NUM
R.MXC Redline Max Cool Stages 0to3 2 MAXCREDL
S.MXC Loadshed Max Cool Stages 0to3 2 MAXCSHED
R.MXH Redline Max Heat Stages 0to2 2 MAXHREDL
S.MXH Loadshed Max Heat
Stages
0to2 2 MAXHSHED
Copyright 2012 Carrier Corp. S 7310 W. Mo rris St. S India napolis, IN 46231 Edition Date: 04/12
Manufacturer reser ves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 48---50LC---C01T
Replaces: New
48/50LC