MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN
POINT
ENTR Y
AIR.Q Air Quality Config. IAQ_CFG
IA.CF IAQ Analog Input Config 0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0: no FIOP
1: FIOP
IAQAN CFG
IA.FN IAQ Analog F an Config 0=Never
1=Occupied
2=Always
0 IA QAN FA N
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0 IA QINC FG
II.FN IAQ Switch Fan Config 0=Never
1=Occupied
2=Always
0 IA QINF AN
AQ.M N Econo Min IAQ Position 0 to 100 % 10 IAQM INP
OVR.P IAQ Override Position 0 t o 100 % 100 IAQOVPOS
OA.CF OAQ Analog Input Config 0=No OAQ
1=DCV
2=Lockout OAQ
0 OA QAN CFG
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQL OCK
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW
AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH
DF.ON FanOnAQDifferential 0 to 5000 600 DAQFNON
DF.OF F an Off AQ Differential 0 to 5000 200 DAQFNOFF
I.4M IAQ Sensor Value at 4mA 0 t o 5000 0 IAQ_4MA
I.20M IAQ Sensor Value at 20mA 0 to 5000 2000 IAQ_20MA
O.4M OAQ Sensor Value at 4mA 0 to 5000 0 OAQ_4MA
O.20M OAQ Sensor Value at 20mA 0 to 5000 2000 OAQ_20MA
H.4M RH Sensor Value at 4mA 0to50 % 0 RH_4MA
H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH_20MA
ALM.O Alarm Relay Config. ALM_CFG
A.SPC SPT/SPRH Sensor Failure No/Y es Yes SP ACE_AL
A.SRT SAT/RAT Sensor F ailure No/Y es Yes SATRAT AL
A.OAT OAT Thermistor Failure No/Yes Yes OAT _AL
A.CS Current Sensor F ailure No/Yes No CS _ AL
A.CMP Compressor Failure No/Y es Yes COMP_AL
A.CKT Refrig Circuit Failure No/Y es Yes CKT_AL
A.SSP SSP Transducer Failure No/Yes Yes SSP_ A L
A.SCT SCT Thermistor Failure No/Yes Yes SCT_AL
A.FAN Indoor Fan Failure No/Yes Ye s FAN_AL
A.FIL Dirty Filter No/Yes Yes FILT_AL
A.TST Thermostat Failure No/Yes Yes TSTAT_AL
A.ECO Economizer Failure No/Y es Yes ECON_AL
PID PID Configurations PID_CFG
EC.P Economizer PID --- kP 0.00 to 99.90 2.5 ECONO_P
EC.I Economizer PID --- kI 0.00 to 99.90 0.12 ECON O_I
EC.D Economizer PID --- kD 0.00 to 99.90 1 EC ON O_D
EC.DT Economizer PID --- rate 10.00 to 180.00 secs 15 ECON O_DT
EC.DB Economizer PID Deadband 0to25 % 3 ECONBAND
LK.P Linkage Staging PID --- kP 0.00 to 99.90 10 LINK_P
LK.I Linkage Staging PID --- kI 0.00 to 99.90 5 LINK_I
LK.D Linkage Staging PID --- kD 0.00 to 99.90 5 LINK_D
LK.DT Linkage Staging PID - -- rate 10.00 to 180.00 secs 30 LINK_DT
(GENERIC = CCN only) GENERICS
POINT 01 Definition Point_01
POINT 02 Definition Point_02
POINT 03 Definition Point_03
POINT 04 Definition Point_04
POINT 05 Definition Point_05
POINT 06 Definition Point_06
POINT 07 Definition Point_07
POINT 08 Definition Point_08
POINT 09 Definition Point_09
POINT 10 Definition Point_10
POINT 11 Definition Point_11
POINT 12 Definition Point_12
POINT 13 Definition Point_13
POINT 14 Definition Point_14
POINT 15 Definition Point_15
POINT 16 Definition Point_16
POINT 17 Definition Point_17
POINT 18 Definition Point_18
POINT 19 Definition Point_19
POINT 20 Definition Point_20
48/50LC