Unit installation
80
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFA ULT
CCN TABLE/
S u b --- T A B L E
CCN
POINT
ENTR Y
HEAT Heating Configuration HEAT_CFG
HT.TY Type of Heat Installed 0=No Heat
1=Gas
2=Electric
0 (50 s eries with no electric h eat)
1(48series)
2 (50 s eries with elec tric heat)
HEATTY P E
N.HTR Number of Heat Stages 1to2 2 ( all excep t below)
1 (48 s eries L ow Nox or s in g le
phase unit)
1 (50 s eries with low or med iu m
heat)
1 (50 seri es 04--- 05 with high heat)
NUM_HEAT
MRT.H Heat Minimum On Time 60 to 999 sec 120 HMI N_ON
MOT.H Heat Minimum Off Time 60 t o 999 sec 120 HMIN_OFF
H.DEC Heat Stage Decrease Time 120 to 999 sec 300 HSTAGD E C
H.INC Heat Stage Increase Time 120 t o 999 sec 450 HSTAGIN C
FOD.E Fan ---off Delay, Elect Heat 10 to 600 sec 30 ELEC_FOD
FOD.G Fan---off Delay, Gas Heat 45 to 600 sec 45 GAS _FOD
HT.LO Heating Lockout Temp 40 to 125 °F 75 OA T LHEAT
SAT
SAT.H SAT Heat Mode Sensing Disable/Enable Disable SAT_HEAT
SAM.L Ma ximum SAT Lower Level 85 t o 200 °F 140 SATMAX_L
SAM.U Maximum SAT Upper Level 85 to 200 °F 160 SATMAX_H
SPT Space Temperature
HT.PD SPT Heat Demand (+)
Level
0.5 to 5 ^F 1 HDE M _POS
HT.ND SPT H eat Demand (---)
Level
--- 5 t o --- 0 . 5 ^F --- 1 HDEM_NEG
H.LAG Heat Thermal Lag Factor 0to5 1 HEA T_LAG
ECON Economizer Configuration ECON_CFG
EC.EN Economizer Installed No/Yes No: no FIOP
Yes: FIOP
ECONO
E.CTL Economizer Control Type 1=Dig/Position
2=Dig/Command
3=Analog Ctrl
1 ECON_CTL
MP.25 Econ Min at 25% Fanspeed 0 to 100 % 0 MINP_25
MP.50 Econ Min at 50% Fanspeed 0 to 100 % 0 MINP_50
MP.75 Econ Min at 75% Fanspeed 0 to 100 % 0 MINP_75
MP.MX Econ Min a t Max Fanspeed 0 to 100 % 30 MINP_MAX
MP.LO Econ Min at Low Fanspeed 0 to 100 % 40 MINP_L OW
MP.VT Econ Min at Vent Fanspeed 0 to 100 % 50 MINPVENT
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONO-
MAX
M.ANG Min Actuator Ctrl Angle 75 t o 90 88 MINANGLE
EH.LO Econo Cool Hi Temp Limit 40 to 100 °F 65 OAT L EC LH
EL.LO Econo Cool Lo Temp Limit ---30 to 50 °F 0 OA T LE CL L
DF.DB Diff Dry Bulb Control Disable/Enable Disable DIFFBULB
UEFC Unoccupied Free Cooling 0=Disabled
1=Unoccpied
2=PreOccupancy
2 UEFC_CFG
FC.TM Free Cool PreOcc Time 1 to 9999 mins 120 UEFCTIME
FC.LO Free Cool Lo w Temp Limit ---30 to 70 °F 50 OA TL U EFC
PE.EN Power Exhaust Installed No/Y es No PE_ENABL
PE.1 PE Stage1 Econo Position 0 to 100 % 40 PE1_POS
PE.2 PE Stage2 Econo Position 0 to 100 % 75 PE2_POS
PE1C Power Exhaust Stage1
CFM
0 to 15000 CFM 800 PE1_CFM
PE2C Power Exhaust Stage2
CFM
0 to 15000 CFM 0 PE2_CFM
IDF.C Indoor Fan Max Speed
CFM
500 to 15000 CFM 1200 (04)
1600 (05)
2000 (06)
IDF_CFM
EN.SW Enthalpy Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
ENTHLCFG
E.TRV Economizer Travel Time 5 to 300 secs 150 ECONOT RV
E.MXB Bottom Stage Max Econo 0 to 100 % 50 ECONMAXB
48/50LC