Unit installation

79
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN
POINT
ENTR Y
I.FAN INDOOR FAN CONFIG AFAN_CFG
FTYP Indoor Fan Type 1=LEN VFD
2=ECM
1
2: Direct Drive Fan
FAN_TYPE
NSPD Number of Speeds 2or3 0 NUM_SPDS
SMT.F Smart Fan Control No/Yes Yes
No (Direct Drive Fan)
SMARTFAN
OC.FN FanOnWhenOccupied No/Y es Yes OCC_FAN
IDF.F Shut Down on IDF Failure No/Yes Yes FATALFAN
FS.MX Supply Fan M aximum Speed 80 to 100 100 SPEEDMAX
F. S P 1 Supply Fan Speed 1 0 to 100 70 (04)
57 (05 & 06)
SPEED1
F. S P 2 Supply Fan Speed 2 0 to 100 87 (04)
71 (05)
69 (06)
SPEED2
F. S P 3 Supply Fan Speed 3 0 to 100 92 (04)
84 (05 & 06)
SPEED3
FS.VN Fan Speed --- Ventilation 0 to 100 % 50 FSPDV EN T
S.VFD SUPPLY F AN VFD CONFIG
N.VLT VFD1 Nominal Motor Volts 0 to 999 volts 230
460
575
VFD1NVL T
N.AMP VFD1 Nominal Motor Amps 0 to 999 amps See VFD Motor P aram eter s
(Table 26 )
VFD1NAMP
N.FRQ VFD1 Nominal Motor Freq 10 to 500 60 VFD1NFRQ
N.RPM VFD1 Nominal Motor RPM 50 to 30000 1725 VFD1NRPM
N.PWR VFD1 Nominal Motor HPwr 0 to 500 See VFD Motor P ar ameter s
(Table 26 )
VFD1NPWR
MAX.A VFD1 M aximum Amps 0 to 999 amps See VFD Motor P aram eters
(Table 26 )
VFD1MAXA
M.DIR VFD1 Motor Direction 0=FORWARD
1=REVERSE
0 VFD1MDIR
ACCL VFD1 Acceleration Time 0 to 1800 secs 30 VFD1ACCL
DECL VFD1 Deceleration Time 0 to 1800 secs 10 VFD1DECL
SW.FQ VFD1 Switching Frequency 0to3 1 VFD1SWFQ
COOL Cooling Configuration COOL_CFG
N.STG Number of Stages 1to2 2 NUM_STAG
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON
MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OFF
RST.C Runtime to Reset Strikes 120 t o 999 sec 300 MIN_ON_S
C.DEC Cool Stage Decrease Time 120 t o 999 sec 300 STAGEDEC
C.INC Cool Stage Increase Time 120 to 999 sec 450 STAGEINC
FOD.C Fan---off Delay, Mech Cool 0 to 600 sec 75 COOL_FOD
FTT Fan Transition Time 60 to 600 sec 480 FANTRANT
ALM.N Alert Each Strike No/Y es Yes ALM_NOW
CA.LO CircuitALockoutTemp 0 to 100F °F 0 OA T LC MPA
LA.SP Low Ambient ODF
Setpoint
0to80 °F 40 LAODF_SP
D.CMP Diagnose Comp Safety No/Y es Yes DIAGCOMP
MX.SA Max Suction Change CirA 0 to 100 PSIG 4 MAXDSSPA
CS.A1 Current Sensing A1 Disable/Enable Disable A1_SENSE
DHUM Dehum Control Type 0=No Control
1=Max Dehum
2=Max Comfort
0 DEHUMCTL
SAT Supply Air Temperature
SA.PD SAT Cool Demand (+)
Level
0.5 to 10 ^F 1 SAT_POS
SA.ND SAT Cool Demand (---)
Level
--- 1 0 t o --- 0 . 5 ^F --- 1 SAT_NEG
SAT.U Minimum SAT Upper Level 35.0 to 65.0 °F 52 SATMIN_H
SAT.L Minimum SAT Lower Level 35.0 to 65.0 °F 40 SATMIN_L
SPT Space Temperature
CL.PD SPT Cool Demand (+)
Level
0.5 to 5 ^F 1 DEM_POS
CL.ND SPT Cool Demand (---)
Level
--- 5 t o --- 0 . 5 ^F --- 1 DEM_NEG
C.LAG Cool Thermal Lag Factor 0to5 1 COOL_LA G
SST Low Suction Control
SST.O Suction OK Temperature 10 to 50 °F 18 SS TOK
SST.1 Low Suction --- Level 1 10 to 50 °F 20 SSTLEV 1
SST.2 Low Suction --- Level 2 5to50 °F 15 SS TLEV2
SST.3 Low Suction --- Level 3 0to50 °F 10 SS TLEV3
CK.DL Delay On Low SST Check 0 to 300 sec 0 SS TCKDLY
FLSU FanLowSuctionTemp 28 to 50 °F 32 FANLOSUC