Unit installation

72
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
PAGE
NO .
ALM.O Alarm Relay Config. ALM_CFG
A.SPC SPT/SPRH Sensor F ailure No/Y es Yes SPACE_AL
A.SRT SAT/RAT Sensor Failure No/Yes Yes SATRATAL
A.OAT OAT Thermistor Failure No/Y es Yes OAT_AL
A.CS Current Sensor F ailure No/Y es No CS_AL
A.CMP Compressor Failure No/Yes Ye s COMP_AL
A.CKT Refrig Circuit Failure No/Y es Yes CKT_AL
A.SSP SSP Transducer Failure No/Yes Yes SSP_AL
A.SCT SCT Thermistor Failure No/Y es Yes SCT_AL
A.FAN Indoor Fan Failure No/Yes Yes FAN_AL
A.FIL Dirty Filter No/Yes Ye s FILT_AL
A.TST Thermostat Failure No/Y es Yes TST AT_AL
A.ECO Economizer Failure No/Yes Yes ECON_AL
PID PID Configurations PID_CFG
EC.P Economizer PID --- kP 0.00 to 99.90 2.5 ECONO_P
EC.I Economizer PID --- kI 0.00 to 99.90 0.12 ECONO_I
EC.D Economizer PID --- kD 0.00 to 99.90 1 ECONO_D
EC.DT Economizer PID --- rate 10.00 to 180.00 secs 15 ECONO_DT
EC.DB Economizer PID Deadband 0to25 % 3 ECONBAND
LK.P Linkage Staging PID --- kP 0.00 to 99.90 10 LINK_P
LK.I Linkage Staging PID --- kI 0.00 to 99.90 5 LINK_I
LK.D Linkage Staging PID --- kD 0.00 to 99.90 5 LINK_D
LK.DT Linkage Staging PID - -- rate 10.00 to 180.00 secs 30 LINK_DT
(GENERIC = CCN only) GENERICS
POINT 01 Definition Point_01
POINT 02 Definition Point_02
POINT 03 Definition Point_03
POINT 04 Definition Point_04
POINT 05 Definition Point_05
POINT 06 Definition Point_06
POINT 07 Definition Point_07
POINT 08 Definition Point_08
POINT 09 Definition Point_09
POINT 10 Definition Point_10
POINT 11 Definition Point_11
POINT 12 Definition Point_12
POINT 13 Definition Point_13
POINT 14 Definition Point_14
POINT 15 Definition Point_15
POINT 16 Definition Point_16
POINT 17 Definition Point_17
POINT 18 Definition Point_18
POINT 19 Definition Point_19
POINT 20 Definition Point_20
TRIM Sensor Calibration (CCN TRIM --- see
Maintenance Display)
SPT.C Space Temp Calibration --- 30 to 130 °F 37
SPT.T Space Temp T rim ---30 to 30 ^F 0 37
SAT.C Supply Air Temp Calib. ---30 to 130 °F 37
SAT.T Supply Air Temp Trim --- 30 to 30 ^F 0 13
RAT.C Return Air Te mp Calib. --- 30 to 130 °F 37
RAT.T Return Air Temp Trim --- 30 to 30 ^F 0 37
CCN CCN Configuration CCN CONFIGURATION
CCN.A CCN Element Number 1 to 239 1 48_50_LC CCNADD 24
CCN.B CCN Bus Number 0 to 239 0 CCNBUS 24
BAUD CCN Baud Rate 1=2400
2=4800
3=9600
4=19200
5=38400
3 CCNBAUDD 24
BROD CCN Broadcast Config. BRODEFS
B.TIM CCN Time/Date Broadcast No/Y es No CCNBC 24
B.OAT CCN OAT Broadcast No/Y es No OATBC 24
B.GS Global Schedule Broadcst No/Yes No GSBC 24
B.ACK CCN Broadcast Ack’er No/Y es No CCNBCACK 24
48/50LC