Unit installation
71
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
PAGE
NO .
ECON Economizer Configuration ECON_CFG
EC.EN Economizer Installed No/Y es No: no FIOP
Yes: FIOP
ECONO 20
E.CTL Economizer Control Type 1=Dig/Position
2=Dig/Command
3=Analog Ctrl
1 ECON_CTL 20
MP.25 Econ Min at 25%
Fanspeed
0 to 100 % 0 MINP_25 21
MP.50 Econ Min at 50%
Fanspeed
0 to 100 % 0 MINP_50 21
MP.75 Econ Min at 75%
Fanspeed
0 to 100 % 0 MINP_75 21
MP.MX Econ Min at Max Fanspeed 0 to 100 % 30 MINP_MAX 20
MP.LO Econ Min at Low Fanspeed 0 t o 100 % 40 MINP_LOW 20
MP.VT Econ Min at Vent
Fanspeed
0 to 100 % 50 MINPVENT 20
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONOMAX
M.ANG Min Actuator Ctrl Angle 75 t o 90 88 MINANGLE 20
EH.LO Econo Cool Hi Temp Limit 40 to 100 °F 65 OATLECLH 21
EL.LO Econo Cool Lo Temp Limit --- 30 to 50 °F 0 OATLECLL 21
DF.DB Diff Dry Bulb Control Disable/Enable Disable DIFFBULB 21
UEFC Unoccupied Free Cooling 0=Disa bled
1=Unoccpied
2=PreOccupancy
2 UEFC_CFG 21
FC.TM Free Cool PreOcc Time 1 to 9999 mins 120 UEFCTIME 21
FC.LO Free Cool Low Temp Limit ---30 to 70 °F 50 OATLUEFC 21
PE.EN Power Exhaust Installed No/Yes No PE_ENABL 21
PE.1 PE St age1 Econo Position 0 to 100 % 40 PE1_POS 21
PE.2 PE St age2 Econo Position 0 to 100 % 75 PE2_POS 22
PE1C Power Exhaust Stage1
CFM
0 to 15000 CFM 800 PE1_CFM
PE2C Power Exhaust Stage2
CFM
0 to 15000 CFM 0 PE2_CFM
IDF.C Indoor Fan Max Speed
CFM
500 to 15000 CFM 1200 (04)
1600 (05)
2000 (06)
IDF_CFM 7
EN.SW Enthalpy Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
ENTHLCFG 9
E.TRV Economizer Travel Time 5 t o 300 secs 150 ECONOTRV
E.MXB Bottom Stage Max Econo 0 t o 100 % 50 ECONMAXB 21
AIR.Q Air Quality Config. IAQ_CFG
IA.CF IAQ Analog Input Config 0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0: no FIOP
1: FIOP
IAQANCFG 9
IA.FN IAQ Analog Fan Config 0=Never
1=Occupied
2=Always
0 IAQANFAN 22
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0 IAQINCFG 23
II.FN IAQ Switch Fan Config 0=Never
1=Occupied
2=Always
0 IAQINFAN 23
AQ.M N Econo Min IAQ Position 0 to 100 % 10 IAQMINP 22
OVR.P IAQ Override Position 0 to 100 % 100 IAQOVPOS 22
OA.CF OAQ Analog Input Config 0=No OAQ
1=DCV
2=Lockout OAQ
0 OAQANCFG 22
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK 21
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW 22
AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH 22
DF.ON FanOnAQDifferential 0 to 5000 600 DAQFNON 23
DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF 23
I.4M IAQ Sensor Value at 4mA 0 to 5000 0 IAQ_4MA 22
I.20M IAQ Sensor Value at 20mA 0 to 5000 2000 IAQ_20MA 22
O.4M OAQ Sensor Value at 4mA 0 to 5000 0 OAQ_4MA 23
O.20M OAQ Sen s or V al u e at 20m A 0 to 5000 2000 OAQ_20MA 23
H.4M RH Sensor Value at 4mA 0to50 % 0 RH_4MA 17
H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH_20MA 17
48/50LC