Unit installation

69
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — CONFIGURATIONS
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
PAGE
NO .
CONFIGURATION SERVICE
CONFIGURATION
DISP Display Configuration DISPLAY
METR Metric Display Off/On Off DISPUNIT 12
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE 12
PROT Password Enable Disable/Enable Enable PASS_EBL 12
PSWD Service Password 0000 to 9999 1111 PAS SWORD 12
TEST Test Display L EDs Off/On Off (di s pl ay only, not in table) DISPTEST 12
UNIT Unit Configuration UNIT
S.DLY Startup Delay 10 to 600 sec 30 STARTDLY 12
U.CTL Unit Control Type 2=Thermostat
3=Space Sensor
2 CTL_TYPE 12
T. C T L Thermostat Control Type 0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 STATTYPE 12
FN.SW Fan Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 FANSTCFG 12
FL.SW Filter Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 FILSTCFG 12
FS.SW Fire Shutdown Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG 12
RM.SW Remote Occupancy Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG 13
SAT.T SAT Settling Time 10 to 900 sec 240 SAT_SET 13
RAT.S RAT Sensor Installed No/Y es Yes RAT_SENS 13
RH.S RH Sensor on OAQ Input No/Yes No RH _OAQ 13
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG 13
TCS.C Temp Cm p S trt Cool Fac tr 0to60 mins 0 TCSTCOOL 13
TCS.H TempCmpStrtHeatFactr 0to60 mins 0 TCSTHEAT 13
I.FAN INDOOR FAN CONFIG AFAN_CFG
FTYP Indoor Fan Type 1=LEN VFD
2=ECM
1
2: Direct Drive Fan
FAN_TYPE 15
NSPD Number of Speeds 2or3 0 NUM_SPDS 15
SMT.F Smart Fan Control No/Yes Yes
No (Direct Drive Fan)
SMARTFAN 16
OC.FN FanOnWhenOccupied No/Y es Ye s OCC_FAN 15
IDF.F Shut Down on IDF Failure No/Y es Ye s FATALFAN 15
FS.MX Supply F an Maximum
Speed
80 to 100 100 SPEEDMAX 15
F. S P 1 Supply Fan Speed 1 0 to 100 70 (04)
57 (05 & 06)
SPEED1 16
F. S P 2 Supply Fan Speed 2 0 to 100 87 (04)
71 (05)
69 (06)
SPEED2 16
F. S P 3 Supply Fan Speed 3 0 to 100 92 (04)
84 (05 & 06)
SPEED3 16
FS.VN Fan Speed --- Ventilation 0 to 100 % 50 FSPDVENT 16
S.VFD SUPPLY FAN VFD CON FIG 15
N.VLT VFD1 Nominal Motor Volts 0 to 999 volts 230
460
575
VFD1NVL T 55
N.AMP VFD1 Nominal Motor Amps 0 to 999 amps See VFD Motor Param eters
(Table 26 )
VFD1NAMP 55
N.FRQ VFD1 Nominal Motor Freq 10 to 500 60 VFD1NFRQ 55
N.RPM VFD1 Nominal Motor RPM 50 to 30000 1725 VFD1NRPM 55
N.PWR VFD1 Nominal Motor HPwr 0 to 500 See VFD Motor Par am eters
(Table 26 )
VFD1NPWR 55
MAX.A VFD1 Maximum Amps 0 to 999 amps See VFD Motor P aram eters
(Table 26 )
VFD1MAXA 55
M.DIR VFD1 Motor Direction 0=FORWARD
1=REVERSE
0 VFD1MDIR 55
ACCL VFD1 Acceleration Time 0 to 1800 secs 30 VFD1ACCL 55
DECL VFD1 Deceleration Time 0 to 1800 secs 10 VFD1DECL 55
SW.FQ VFD1 Switching Frequency 0to3 1 VFD1SWFQ 55
48/50LC