Unit installation

68
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — INPUTS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
DISPLAY WRITE
STATUS
INPUTS STATUS DISPLAY
STAT Thermostat Inputs UINPUT
Y1 Thermostat Y1 Input Off/On Y1 forcible forcible
Y2 Thermostat Y2 Input Off/On Y2 forcible forcible
W1 Thermostat W1 Input Off/On W1 forcible forcible
W2 Thermostat W2 Input Off/On W2 forcible forcible
G Thermostat G Input Off/On G forcible forcible
GEN.I General Inputs General Inputs
FIL.S Filter Status Switch Clean/Dirty FILTSTAT forcible
FAN.S Fan Status Switch Off/On FAN_STA T forcible
FDWN Fire Shutdown Switch Off/On FIREDOWN forcible
ENTH Outdoor Enthalpy Switch Low/High ENTHALPY forcible forcible
RM.OC Remote Occupancy Switch Off/On REM_OCC forcible forcible
HUM Space Humidity Switch Low/High HUM_STAT forcible forcible
IGC.F IGC Fan Request Off/On IDF_FDBK
CS.A1 Current Sensing A1 Off/On CS_A1
AIR.Q Air Quality Inputs
IAQ.S IAQ Level (switch) Low/High IAQIN forcible forcible
IAQ IAQ Level (sensor) xxxx IAQ forcible forcible
OAQ OAQ Level (sensor) xxxx OAQ forcible forcible
SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible
MODE — OUTPUTS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
DISPLAY WRITE
STATUS
OUTPUTS STATUS DISPLAY
FANS Fan Outputs UOUTPUT
F. S P D Commanded Fan Speed xxx % FANSPEED
IDF1 Indoor Fan Speed Relay 1 Off/On IDF_1
IDF2 Indoor Fan Speed Relay 2 Off/On IDF_2
IDF3 Indoor Fan Speed Relay 3 Off/On IDF_3
COOL Cool Outputs
CMP.A Circuit A Compressor Off/On COMP_A
LDR.A Circuit A Loader Off/On LOADER
L.ODF Low Ambient Outdoor Fan Off/On LA_ODF
HEAT Heat Outputs
HT.1 Heat Stage 1 Relay Off/On HEAT_1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
ECON Economizer Outputs
EC.CP Econo Commanded Position 0 to 100 % ECONOCMD forcible forcible
EC.AP Econo Actual Position 0 to 100 % ECONOPOS
PE.1 Power Exhaust 1 Relay Off/On PE_1 forcible
PE.2 Power Exhaust 2 Relay Off/On PE_2 forcible
ALRM Alarm Relay Off/On ALMOUT forcible