Unit installation
67
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — SERVICE TEST
ITEM EXPANSION RANGE UNITS CCN TABLE/Sub --- TABLE CCN POINT
SERVICE TEST
TEST Field Service Test Mode Off/On (TEST = display only)
INDP Test Independent Outputs TESTINDP
ECON Economizer Position Test 0 to 100 % S_ECONO
E.CAL Calibrate Economizer Off/On S_ECOCAL
PE.1 Power Exhaust 1 Test Off/On S_PE_1
PE.2 Power Exhaust 2 Test Off/On S_PE_2
ALRM Alarm Relay Test Off/On S_ALMOUT
FANS Te s t Fa n s TESTFANS
F. S P D Indoor Fan Speed Test 0 t o 100 % S_FANSPD
F. M O D IDF Fan Mode 0to7 S_IDFMOD
IDF1 Indoor Fan Test 1 Off/On S_IDF_1
IDF2 Indoor Fan Test 2 Off/On S_IDF_2
IDF3 Indoor Fan Test 3 Off/On S_IDF_3
COOL Test Cooling TESTCOOL
CMP.A Cool A Test Off/On S_COMP_A
LDR_A Cir A Loader Test Off/On S_LOADER
F. S P D Reduced Cool Fan Speed 0 to 100 % S_FSPDCL
L.ODF Low Amb ODF Test Off/On S_LAODF
HEAT Te s t H e a t i n g TESTHEAT
HT.1 Heat Stage 1 Test Off/On S_HEAT_1
HT.2 Heat Stage 2 Test Off/On S_HEAT_2
F. S P D Reduced Heat Fan Speed 0 to 100 % S_FSPDHT
MODE — TEMPERATURES & PRESSURES
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
DISPLAY WRITE
STATUS
TEMPERATURES STATUS DISPLAY
AIR.T Air Temperatures UINPUT
SAT Supply Air Temperature xxx.x °F SAT_DISP
OAT Outdoor Air Temperature xxx.x °F OA_TEMP forcible forcible
SPT Space Temperature xxx.x °F SP ACE_T forcible forcible
SPTO Space Temperature Offset xxx.x ^F SPTO forcible forcible
RAT Return Air Temperature xxx.x °F RETURN_T forcible forcible
REF.T Refrigerant Temperatures xxx.x °F
SST.A Sat. Suction Temp A xxx.x °F SST_A
SCT.A Sat. Condenser Temp A xxx.x °F SCT_A
PRESSURES
SSP.A Suction Pressure A xxx.x psig SSP_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
MODE — SETPOINTS
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/Sub --- TABLE CCN POINT
SETPOINTS SETPOINT CONFIGURATION
OCSP Occupied Cool Setpoint 55 to 80 °F 78 SET_PNT OCSP
UCSP Unoccupied Cool Setpoint 65 to 95 °F 85 UCSP
OHSP Occupied Heat S etpoint 55 to 80 °F 68 OH SP
UHSP Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
GAP Heat---Cool Setpoint Gap 2to10 ^F 5 HCSP_GAP
STO.R SPT Offset Range (+/--- ) 0to5 ^F 5 SPTO_RNG
RH.SP Space RH Occupied SP 30 to 100 % 50 SPRH_SP
RH.UN Space RH Unoccupied SP 30 to 100 % 80 SPRH_USP
RH.DB Space RH Deadband 2to20 % 8 SPRH_DB
RH.HB Dehum Heat SP Deadband --- 5 t o 5 ^F 2 RH_H SPDB
LCSP Low Cool SAT Setpoint 55 to 75 °F 60 LCSASP
HCSP High Cool SAT Setpoint 50 to 70 °F 55 HCSASP
CCSP Comfort SAT Setpoint 40 to 70 °F 55 CFSASP
48/50LC