Unit installation
65
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
S.VFD SUPPLY FAN VFD VFD_DATA
VFD1 Status Word 1 NNNNN VFD1STA T
SPD VFD1 Actual Speed % NNN.n % VFD1_SPD
RPM VFD1 Actual Motor RPM NNNNN VFD1RPM
FREQ VFD1 Actual Motor Freq NNN.n VFD1FREQ
AMPS VFD1 Actual Motor Amps NNN.n amps VFD1AMPS
TORQ VFD1 Actual Motor Torque NNNN.n % VFD1TORQ
PWR VFD1 Actual Motor Power NNNN.nn VFD1PWR
VDC VFD1 DC Bus Voltage NNNN volts VFD1VDC
V.O U T VFD1 Output Voltage NNNN volts VFD1VOUT
TEMP VFD1 T ransistor Temp (C) NNN VFD1TEMP
RUN.T VFD1 Cumulative Run Time NNNNN hours VFD1RUNT
KWH VFD1 Cumulative kWh NNNNN VFD1KWH
LFC VFD1 Last F ault Code NNNNN VFD1LFC
VFD1 DI1 State Open/Close VFD1_DI1
VFD1 DI2 State Open/Close VFD1_DI2
VFD1 DI3 State Open/Close VFD1_DI3
VFD1 DI4 State Open/Close VFD1_DI4
VFD1 DI5 State Open/Close VFD1_DI5
VFD1 DI6 State Open/Close VFD1_DI6
VFD1 AI1 (% of range) NNN.n % VFD1_AI1
VFD1 AI2 (% of range) NNN.n % VFD1_AI2
HRS Component Run Hours STRTHOUR
A1 Compressor A1 Run Hours xxxxx.xx hours HR_A1 forcible
A.LDR Comp A1 Loader Run Hours xxxxx.xx hours HR_A1LDR
IDF1 Indoor Fan 1 Run Hours xxxxx.xx hours HR_IDF1 forcible
IDF2 Indoor Fan 2 Run Hours xxxxx.xx hours HR_IDF2
IDF3 Indoor Fan 3 Run Hours xxxxx.xx hours HR_IDF3
HT.1 Heat Stage 1 Run Hours xxxxx.xx hours HR_HTR_1 forcible
HT.2 Heat Stage 2 Run Hours xxxxx.xx hours HR_HTR_2 forcible
PE.1 Power Exhaust1 Run Hours xxxxx.xx hours HR_PE_1 forcible
PE.2 Power Exhaust2 Run Hours xxxxx.xx hours HR_PE_2 forcible
ALRM Alarm Relay Run Hours xxxxx.xx hours HR_ALM forcible
L.ODF Low Amb ODF Run Hours xxxxx.xx hours HR_LAODF forcible
STRT Component S tarts
A1 Compressor A1 Starts xxxxxx ST_A1 forcible
A.LDR Comp A1 Loader Starts xxxxxx ST_A1LDR
IDF1 Indoor Fan 1 Starts xxxxxx ST_IDF1 forcible
IDF2 Indoor Fan 2 Starts xxxxxx ST_IDF2
IDF3 Indoor Fan 3 Starts xxxxxx ST_IDF3
HT.1 Heat Stage 1 Starts xxxxxx ST_HTR_1 forcible
HT.2 Heat Stage 2 Starts xxxxxx ST_HTR_2 forcible
PE.1 Power Exhaust 1 Starts xxxxxx ST_PE_1 forcible
PE.2 Power Exhaust 2 Starts xxxxxx ST_PE_2 forcible
ALRM Alarm Relay Starts xxxxxx ST_ALM forcible
L.ODF Low Amb ODF Starts xxxxxx ST_LAODF forcible
(ALRMDISP) = CCN only) ALRMDISP
Active Alarm 1 Code xxx ALMCODE1
Active Alarm 2 Code xxx ALMCODE2
Active Alarm 3 Code xxx ALMCODE3
Active Alarm 4 Code xxx ALMCODE4
Active Alarm 5 Code xxx ALMCODE5
Reset All Current Alarms No/Yes ALRESET forcible
Reset Alarm History No/Yes ALHISCLR forcible
48/50LC