Unit installation

64
APPENDIX — LOCAL DISPLAY AND CCN TABLES
MODE — RUN STATUS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
RUN ST A TUS STATUS DISPLAY
VIEW Auto View of Run Status (VIEW = Display only)
HVAC HVAC Mode Status 1=Disabled
2=Ventilation
3=Cool
4=Heat
HVACMODE
OCC Currently Occupied No/Y es OCCUPIED
SAT Supply Air Temperature xxx..x °F SAT_DISP
ALRM Current Alarms & Alerts xx ALRMALRT
TIME Time of Day xx.xx hh.mm TIMECOPY
VERS Software Version Numbers VERSIONS
MBB CESR131505---xx--- xx ( x x --- x x i n t a b l e ) MODEL_NUMBER_01
ECB CESR131249--- xx--- xx MODEL_NUMBER_02
MARQ CESR131171---xx--- xx MODEL_NUMBER_03
VFD1 FW Version --- xxxxx VFD1_SW
NAVI CESR131227---xx--- xx
MODE Control Modes MODEDISP MODEDISP
SYS Current System Mode 1=Disabled
2=Run Enabled
3: Service Test
SYS_MODE
HVAC Current HVAC Mode 1=Disa bled
2=Ventilation
3=Cool
4=Heat
HVACMODE
F. MO D Indoor Fan Mode x IDF_MODE
HV.DN Remote HVAC Mode Disable No/Yes HVACDOWN forcible
EFF.C Cool Setpoint In Effect xx.x °F CSP_EFF
EFF.H Heat Setpoint In Effect xx.x °F HSP_EFF
OCC Currently Occupied No/Y es OCCUPIED forcible
T. O V R Timed Override in Effect No/Y es MODETOVR
LINK Linkage Active No/Y es MODELINK
D.LMT Demand Limit In Effect No/Y es MODEDMDL
C.LOC Compressor OAT Lockout No/Yes COMPLOCK
H.LOC Heat OAT Lockout No/Yes HEATLOCK
OK.EC OK to Use Economizer? No/Yes ECONCOOL
COOL Cooling Status COOLDISP
DMD.C Cooling Demand xxx.x ^F COOL_DMD
AVL.C Available Cooling Stages x AVLCSTGS
REQ.C Requested Cooling Stages x REQCSTGS
MAX.C Max Allowed Cool Stages x MAXCSTGS forcible
LMT.C Max Cool Stage In Effect x CSTGLIMT
F. S P D Commanded Fan Speed xxx % FANSPEED
CMP.A Circuit A Compressor Off/On COMP_A
TG.A Timeguard A xxx sec TIMGD_A
LDR.A Circuit A L oader Off/On LOADER
TG.L Timeguard Loader xxx sec TIMGD_L
SST.A Sat. Suction Temp A xxx.x °F SST_A
SSP.A Suction Pressure A xxx.x psig SSP_A
SCT.A Sat. Condenser Temp A xxx.x °F SCT_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD
AVL.H Available Heating Stages x AVL HSTGS
REQ.H Requested Heating Stages x REQHSTGS
MAX.H Max Allowed Heat Stages x MAXHSTGS forcible
LMT.H Max Heat Stage In Effect x HSTGLIMT
F. S P D Commanded Fan Speed xxx % FANSPEED
HT.1 Heat Stage 1 Relay Off/On HEAT_1
TG.H1 Heat Stage 1 Timeguard xxx sec TIMGD_H1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
TG.H2 Heat Stage 2 Timeguard xxx sec TIMGD_H2
ECON Economizer St atus ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP MinPositioninEffect xxx % MIN_POS forcible
IAQ.S IAQ Level (switch) Low/High IAQIN
IAQ IAQ Level (sensor) xxxx IAQ
OAT Outdoor Air Temperature xxx.x °F OA_TEMP
RAT Re turn Air Temperature xxx.x °F RETURN_T
ENTH Outdoor Enthalpy Switch Low/High ENTHALPY
OAQ OAQ Level (sensor) xxxx OAQ
PE.1 Power Exhaust 1 Relay Off/On PE_1
PE.2 Power Exhaust 2 Relay Off/On PE_2
48/50LC