IEC 947-2 Interrupting Ratings
In addition to UL 489 and ANSI C37-13, MASTERPACT circuit breakers comply with the IEC 947-2
Standard as per the table below. For further information, contact a sales representative.
Type Ampere Interrupting Ratings
3-Pole Rating (A) UL489 IEC 947-2
RMS Symmetrical Amps
480 Vac 600 Vac Short-time 440 Vac 690 Vac
Icu Ics Icu Ics
Standard Interrupting Rating
MP08 H1 800 65 kA 65 kA 50 kA 65 kA 65 kA 65 kA 65 kA
MP12 H1 1200 65 kA 65 kA 50 kA 65 kA 65 kA 65 kA 65 kA
MP16 H1 1600 65 kA 65 kA 50 kA 65 kA 65 kA 65 kA 65 kA
MP20 H1 2000 75 kA 75 kA 75 kA 75 kA 75 kA 75 kA 75 kA
MP25 H1 2500 75 kA 75 kA 75 kA 75 kA 75 kA 75 kA 75 kA
MP30 H1 3000 75 kA 75 kA 75 kA 75 kA 75 kA 75 kA 75 kA
MP40 H1 4000 100 kA 100 kA 100 kA 100 kA 100 kA 85 kA 85 kA
MP50 H1 5000 100 kA 100 kA 100 kA 100 kA 100 kA 85 kA 85 kA
MP63 H1 6300 (1) 100 kA 100 kA 100 kA 100 kA 100 kA 85 kA 85 kA
High Interrupting Rating
MP08 H2 800 100 kA 65 kA 50 kA 100 kA 100 kA 85 kA 85 kA
MP12 H2 1200 100 kA 65 kA 50 kA 100 kA 100 kA 85 kA 85 kA
MP16 H2 1600 100 kA 65 kA 50 kA 100 kA 100 kA 85 kA 85 k A
MP20 H2 2000 100 kA 75 kA 75 kA 100 kA 100 kA 85 kA 85 kA
MP25 H2 2500 100 kA 75 kA 75 kA 100 kA 100 kA 85 kA 85 kA
MP30 H2 3000 100 kA 75 kA 75 kA 100 kA 100 kA 85 kA 85 kA
MP40 H2 4000 125 kA 100 kA 100 kA 150 kA 125 kA 85 kA 85 kA
MP50 H2 5000 125 kA 100 kA 100 kA 150 kA 125 kA 85 kA 85 kA
MP63 H2 6300 (1) 150 kA 100 kA 100 kA 150 kA 125 kA 85 kA 85 kA
(1) Not UL Listed.