Technical data

11/98
©1995 Square DAll Rights Reserved
64
Appendix
Endurances
A–Endurance Without Maintenance
MASTERPACT 08 12 16 20 25 30 - 32 40 50 63
MP or MC
Mechanical 12,500 10,000 10,000 10,000 10,000 10,000 5,000 5,000 5,000
Electrical 480 Vac 10,000 10,000 10,000 9,000 8,000 4,000 3,000 3,000 2,000
600 Vac 10,000 10,000 10,000 7,000 6,000 2,600 2,500 2,500 1,500
B–Endurance With Service Maintenance
Electrical (480 Vac) or Mechanical
20,000 20,000 20,000 15,000 15,000 15,000 10,000 10,000 10,000
C–Endurance Required by Standards
Frame size 800 1200 1600 2000 2500 3000 4000 5000 6300
UL489 Mechanical 3,500 2,000 2,000 2,000 2,000 1,500 1,500 1,500 1,500
Electrical 500 500 500 500 500 400 400 400 400
ANSI Mechanical 12,500 NS 4,000 4,000 NS 1,500 1,500 NS NS
Electrical 2,800 NS 800 800 NS 400 400 NS NS
Important Notice:
All endurances given are based on normal operating conditions and conventional tests:
n Closing and opening operations at rated current
n Power factor: 0.75–0.80
As actual conditions differ, use these values only as inspection guidelines and periodically check
contact wear.
Under normal operating conditions of use, as determined by UL 489 or ANSI Standards (see table
C) and controlled by tests, MASTERPACT circuit breakers do not require maintenance. However,
these circuit breakers exceed, without maintenance and additional costs, the endurances required
by standards. See tables A and C. Service maintenance by a field service representative will extend
the endurance according to table B. This service can be performed on site and consists in changing
contacts, arc chutes and some other parts.
Example:
MP16 at 480 V requires no maintenance before 10,000 cycles (mechanical or electrical). Endurance
may be increased after servicing at 10,000 operations.