Technical data
63
©1995 Square D—All Rights Reserved
11/98
Appendix
Insulation Resistance Tests
When circuit breakers are subjected to severe operating conditions, an insulation resistance test
may be performed as indicated in NEMA standard publication No. AB4-1991. An insulation
resistance test is used to determine the quality of the insulation between phases and phase-to-
ground. The resistance test is made at a dc voltage higher than the rated voltage to determine the
actual resistance of the insulation. The most common method employs a "megger" type instrument.
A 1000-volt instrument will provide a more reliable test because it is capable of detecting tracking on
insulated surfaces. Investigate resistance values below 1 megohm. The insulation test shall be
made:
n Between line and load terminals of individual poles with the circuit breaker contacts open
n Between adjacent poles and from poles to the metallic supporting structure with the circuit
breaker contacts closed
This test may be made with the circuit breaker in place after the line and load conductors have been
removed, or with the circuit breaker bolted to a metallic base which simulates the in-service
mounting.
Electrical Tests
These tests require equipment for pole resistance measurement and for overcurrent and
instantaneous tripping in accordance with NEMA Standard publication No. AB4. They are not within
the scope of normal field operation.