Interlocking Rods and Cables
Two or three MASTERPACT circuit breakers can be mechanically interlocked by means of rods or
cables. This accessory is mountable on the right side of the circuit breaker. This adaptation can be
made on site without modifying the circuit breaker.
Mechanical Interlock Between Two or Three Stacked Circuit Breakers
This interlocking is obtained by the joining of:
n One adaptation block
n One or two adjustable and nonadjustable rods
Maximum distance between the two fixing surfaces of the devices: 35 in. (0.89 m)
Mechanical Interlocks Between Two Side-by-Side Circuit Breakers
This interlocking is obtained by the joining of:
n One adaptation block
n One set of adjustable cables with a maximum length of 78 in. (2 m)
Possible Mounting Arrangements Among Three Stacked Circuit Breakers
One use, power supplied by:
n Two transformers N1 and N2 which are connected in parallel
n Or one standby source G
06313067
06313070 06313069 06313068
G
N2N1
N2N1
C
N1 N2 N3
One use, power supplied by one group of transformers N1, N2 or N3 or of generators, preventing
any connection in parallel.
Two uses, independently powered supply by two transformers N1 and N2, standby through a circuit
breaker or a connection tie switch, preventing the connection in parallel of the two current
transformers.
Accessories