Accessories
24 Additional Auxiliary Switches (OFSUP)
An external plate holds a set of 24 SPDT switches operated by means of a cable. They are
available only for drawout circuit breakers.
06313055
06313056
212
211
F
Open
222
221
F
234
231
O
244
241
O
Closed
06313057
252 254
251
PF
Ready-to-Close
Ready-to-close Switch (PF)
This SPDT switch indicates that the circuit breaker is ready to close and that the following
conditions exist:
n The circuit breaker is open
n The stored energy mechanism is charged
n The control unit is reset
n The circuit breaker opening push button is neither locked nor padlocked
n The circuit breaker is in the fully-connected or test position
The switch is field-installable.
Standard Auxiliary Switches (O and F)
2a + 2b switches available as standard:
n "a" contacts are open when the circuit breaker is open and closed when the circuit breaker is
closed.
n "b" switches are closed when the circuit breaker is open and open when the circuit breaker is
closed.
See page 30 for operating diagrams.